beautypg.com

8 dehumidification management, 9 management of the condenser fan, 10 cabinet light management – EVCO EVFTFT618N7U User Manual

Page 34: 1 management via extractor fan/dehumidifier, 2 management via cooling plant activation

background image

EVCO S.p.A.

EVFTFT618 | Installer manual ver. 2.2 | Code 144FTFT618E224

Page

34

of

62

10.8 Dehumidification management

Dehumidification management is only active when the humidity management takes place via the use of the humidity

transducer (rU0 = 0).

The dehumidification can be managed in two different ways: via an extractor fan (parameter u3 = 0, utility associated to

output K4) or via the activation of the cooling plant (compressor and pump-down electrovalve if present).

10.8.1 Management via extractor fan/dehumidifier

In the case of management via extractor fan/dehumidifier, the output will activate when the humidity has exceeded the

dehumidification neutral area, (rU6) of the value of the differential value (rU5) and deactivates when the humidity has

returned within the dehumidification neutral area value.

10.8.2 Management via cooling plant activation

The compressor will behave in the same way whenever the management of the pump-down electrovalve is enabled.

If, instead, pump-down electrovalve management is enabled, there will first be a dehumidification attempt via activation

of the electrovalve (rU7, to try and make use of the high pressure generated during pump-down in compressor switch-off

mode), on the expiry of which, the compressor output will be activated.

Once the humidity returns within the dehumidification neutral area value, the pump-down electrovalve will be deactivated.

After which, the compressor will deactivate via the pump-down algorithm.

10.9 Management of the condenser fan

If parameter u3 has value 1, output K4 will assume condenser fan control function.

If the condenser probe is active (parameter P4 = 1), the condenser fan will activate when the condenser temperature is

over the value of parameter F16 of the differential value (F16 + 2.0 °C / 4 °F), independently from the status of the

compressor, while it will always be on with the compressor on.

The condenser fan will switch-off when the condenser temperature drops below the value of parameter F16.

With condenser probe disabled (parameter P4 = 0) the condenser fan will be activated in parallel to the compressor, while

deactivation will be delayed by the time established with parameter F17.

The condenser fan is always on during an overheated condenser alarm (label COH) or compressor blocked (label CSd)

alarm.

The fans are handled during the hot gas defrost.

10.10 Cabinet light management

Cabinet light switch-on is enabled/disabled by opening/closing the door.

Light on with door open, light off with door closed.