EVCO EVFTFT618N7U User Manual

Page 42

background image

EVCO S.p.A.

EVFTFT618 | Installer manual ver. 2.2 | Code 144FTFT618E224

Page

42

of

62

0 = seconds

1 = minutes

Par.

Min.

Max.

Unit

Default

Compressor protection

C0

0

240

min

0

compressor switch-on delay from instrument switch-on

C1

0

240

min

2

minimum time between two compressor switch-ons (3)

C2

0

240

min

0

compressor switch off minimum duration

C3

0

240

s

0

minimum duration of compressor switch on time

C4

0

240

min

0

compressor forced switch-on duration and start of recovery,

proving and baking delay phases

C6

0

199

°C

70

condenser

temperature

above

which

the

blocked

overheated condenser alarm is activated (“COH” code)

C7

0

199

°C

80

condenser

temperature

above

which

the

blocked

compressor alarm is activated (“CSd” code)

C8

0

15

min

1

blocked compressor alarm delay (“CSd”code)

Par.

Min.

Max.

Unit

Default

Defrosting

d0

0

99

h

6

defrosting interval

0 = defrosting will never be activated at intervals

d1

0

1

- - - -

0

type of defrosting

0 = electrical (the compressor will be switched off during

defrosting, the defrosting output will be activated

and the evaporator fan will be switched off)

1 = hot gas (the compressor will be switched on during

defrosting, the defrosting output will be activated

and the evaporator fan will be switched off)

d2

-99

99

°C

8

defrosting end temperature (evaporator temperature); see

also parameter d3

d3

0

99

min

30

if parameter P3 is set at 0, duration of defrosting

if parameter P3 is set at 1, maximum duration of

defrosting; see also parameter d2

0 = defrosting will never be activated

d5

0

99

min

30

defrosting

delay

from

start-up

of

storing/manual

refrigeration

0 = defrosting will be started on expiry of the time

established with parameter d0

d7

0

15

min

2

dripping duration (the compressor and the evaporator fan

remain off during dripping and the defrosting output will be

deactivated)

d15

0

99

min

0

minimum duration of compressor switch-on on activation of

defrosting so these can be activated (only if parameter d1

is set at 1)

Par.

Min.

Max.

Unit

Default

Temperature alarms