EVFTFT618 | Installer manual ver. 2.2 | Code 144FTFT618E224

Page

14

of

62

4.1.2 Connection of the RS-485 serial port terminating resistor

The terminating resistor must be connected in order to reduce the reflections on the signal transmitted along the cables

that connect the RS-485 serial port to other EVCO products.

To connect the terminating resistors, position the jumper as illustrated in the following drawing.

To disconnect the terminating resistors, position the jumper as illustrated in the following drawing.

4.2

Warnings for the electric connection

-

do not use electric or pneumatic screwdrivers on the device terminal board

-

if the device has been taken from a cold to hot place, humidity could condense inside; wait about 1 hour before

powering it

-

make sure that the power supply voltage, the frequency and the operational electric power of the device,

correspond with those of the local power supply; see chapter 0

-

disconnect the device power supply before proceeding with any type of maintenance

-

do not use this device as a safety device

-

for repairs and information regarding the device, contact the EVCO sales network.