11.4 Calibration of Remote Meters (cont'd)
Use the following diagram for connecting a Frequency Meter (AM):
Terminal Connection (AM)
AM
Ammeter
CC
Zero adjust
screw
Note: Use a 1 mAdc ammeter or
7.5Vdc voltmeter. Connect the meter
across terminals AM-CC. Use shielded
cable (1000 ft. maximun length).
Use the following procedure to calibrate the (AM) meter:
1
)
2
)
3)
4)
5)
6
)
7)
Start the inverter to output a run frequency such as 60 Hz /-,/ /
j j
Press "down" key while pressing
CLEAR/RESET
to display ;
j— j j
Press either the "up" or "down" key to display
: i—i i i
I I I I
Press the
RUN
key to display :/ [value]
Adjust the analog meter reading to match the digital display reading by pressing
the "up" or "down" keys.
Press the
READ/WRITE
key to store this setting to non-volatile EEPROM
memory.
Press the
CLEAR/RESET
key to return to the normal frequency display
j j j
1 1 - 4