11.0 Output Terminal Operating Functions

The inverter provides terminals for outputting signals to external components. A number of

selectable "operating" output signals, as well as "fault" output signals, are available. These output

signal terminals are located on the terminal board (See Control/Driver Terminal Block Details on

page 5-5).

11.1

Selectable Outputs

The output terminals RCH(UL) and LOW(LL) are multifunctional and are selectable through

function [:0.tb] (See item

6 on page 7-3). The type of selections are

available as shown below:

LL

Outputs

a signal when frequency

is greater than or equal to the LL value.

UL

Outputs

a signal when frequency

is equal to UL value.

LOW

Outputs

a signal when frequency

is greater than or equal to the LOW SPEED

DETECTION VALUE "LF".

RCH Outputs a signal based upon the selection of the RCH parameters rCH, rrCH, FrCH.

All output signals are open-collector with 50mAdc~24Vdc ratings.

The illustrations below show output timing diagrams for the upper and lower frequency limits

and for low speed and speed reach signals.

Upper/lower limit frequency signal output

Low speed/speed reach signal output with [:rCH]=0

Low speed/speed reach signal output with rCH=1