4.2

Selection of Main Circuit Wiring Equipment and
Standard Cable Sizes

Inverter

•Molded case

circuit breaker

(MCCB)

Ampacity

(FLA

X

1.25)

•'Typical cable size (AWG)

Type form

Amp

rating

(A)

(A)

Main power

and

motor load

230Vac and

460Vac control

power source

Frequency

command input,

frequency meter,

ammeter

Other

signal

circuits

Q2-2035

20

13.8

#14

Q2-2055

30

21.9

#12

Q2-2080

50

31.6

#10

Q2-2110

70

40

#8

Q2-2160

90

60

#6

Q2-2220

100

78

#4

Q2-2270

125

98

#3

Q2-2330

150

115

#2

Q2-4055

15

10.9

#14

Q2-4080

30

15.8

#14

Q2-4110

30

20.1

#12

#14

3-core shield cable

(speed reference)

2-core shield cable

#20

#18

Q2-4160

40

30.2

#10

Q2-4220

50

38.8

#8

Q2-4270

70

48.8

#8

Q2-4330

90

57.5

#6

Q2-4400

100

74.8

#4

Q2-4500

100

93.4

#3

Q2-4600

125

110.7

#2

Q2-4800

175

138

#1/0

Q2-410K

200

178.3

#3/0

Q2-412K

225

223

#4/0

Q2-415K

300

268

••• 2(#2/0)

Q2-420K

350

330

••• 2(#4/0)

See next page for notes and precautions.