Standard Specifications (cont'd)

ITEM

STANDARD SPECIFICATIONS

Control

Control Method

Sinusoidal PWM control

Output voltage regulation

Same as power line.

Output frequency

0.0 to 160.0 Hz (0.0 to 60 Hz setting when shipped); maximum
frequencv ranqe is 30 to 160 Hz *1

Frequency setting
resolution

0.1Hz: Operating panel input; 0.03 Hz: Analog input; 0.01Hz:

Input throuqh computer interface (aqainst a 60 Hz)

Frequency accuracy

±0.5% (at 25°C; ±10°C) aqainst the maximum frequency

Voltage/frequency
characteristics

Second-order nonlinear mode for variable torque.
"Max voltage" frequency adjustment (25 to 160 Hz), torque
boost adjustment (0 to 30 %), start-up frequency adjustment
(Oto 10 Hz)

Frequency setting signals

3k ohms potentiometer (a 1 k to 10k ohms-rated potentiometer can
be connected). 0 to 10 Vdc (input impedance: 30k ohms), 0 to
5 Vdc (15k ohms), 4 to 20 mAdc (250 ohms)

Output frequency
characteristics of IV
terminal input signal

Can be set to an arbitrary characteristic by setting 2 points.

Frequency jump

3-point setting; setting jump frequency and band width

Upper/lower limit

frequencies

Upper limit frequency: 0.0 Hz to maximum frequency
Lower limit frequency: 0.0 Hz to upper limit frequency

PWM carrier frequency

switching

Adjusted in the range of 5 kHz to 16 kHz (12 kHz setting when
shipped)

Operating

functions

Acceleration/deceleration
time

0.1 to 1200 seconds, switching of acceleration time 1 or 2,
selection of S-shaped 1 or 2, or selection of acceleration/
deceleration patterns

Electrical braking

DC injection braking

Start-up frequency adjustment (0 to 10 Hz),
braking voltage adjustment (0 to 20 %),
braking time adjustment (0 to 5 seconds)

Forward or reverse run

Forward run when F-CC closed; reverse run when R-CC closed;
reverse run when both F-CC and R-CC closed; coasting stop

when ST-CC open; emergency coast stop by a command from
operating panel

Jogging run

Jogging run engaged when N.O. contact is closed, (adjustment

range 0.0 to 20.0 Hz)

Multispeed run

By opening and closing different combinations of CC, SSI, SS2,
and SS3, the set speed or seven preset speeds can be selected.

Automatic fault latch reset

When a protective function is activated, the system checks main
circuit devices, and attempts the restart up to 5 times (activated
when shipped)

Soft stall

Sustains a run in overload mode (set at ON when shipped)

Automatic restart

Smoothly recovers a normal run of a free-running motor utilizing
motor speed detection control.

Programmable RUN
patterns

Allows setting of 7 different patterns of automatic operation

Protection

Protective functions

Stall prevention, current limit, overcurrent, overvoltage, short-
circuit at load, load-end ground fault, undervoltage, momentary
power interrupt, electronic thermal overload, main circuit over­
current at start-up, load-end overcurrent at start-up, cooling

fin overheat, and emergency stop. Provisions for external
fault signal.

Electronic thermal

characteristics

Standard motor/constant torque V/f motor switching, and
electronic thermal stall prevention activating level adjustment

Reset

Resets inverter when N.O. contact is closed.

Consult the factory for applications above 80 Hz.

3 - 2