beautypg.com

Toshiba – Toshiba Q-Flowsaver II User Manual

Page 32

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

TOSHIBA

7.2

System Parameters Adjustment Range and Factory Settings

PARAMETER

DISPLAY

ITEM

NO.

PARAMETER

DESCRIPTION

ADJUSTMENT

RANGE

FACTORY

SETTING

REFERENCE

PAGE

SETUP PARAMETERS

*

• I ( / 1 /

.I'LL

1

1

Acceleration time #1

0.1 - 1200 sec

90.0 sec

9-1

1 r r 1

• LI L L I

2

Deceleration time #1

0.1 - 1200 sec

120.0 sec

9-1

• I I I

/_i L

3

Upper frequency limit

0.0 Hz - FH

60.0 Hz

9-1

• / /

/_ L

4

Lower frequency limit

0.0 Hz

-

UL

0.0 Hz

9-1

• /~/ (

1 1

5

Terminal IV point #1 setting signal

0-100%

20%

9-1

• r n 1

,

/ “ 1 1

6

Point #1 output frequency

0.0 Hz - FH

0.0 Hz

9-1

• /~/ “(

1

L

7

Terminal IV point #2 setting signal

0-100%

100%

9-1

• /“ n

1

. I

I I -

8

Point #2 output frequency

0.0 Hz - FH

60.0 Hz

9-1

• 1 I I
» 1 - 1 1 1

9

Electronic thermal protection level

10-100%

100%

9-1

• r 1 1

• _/ L L

10

Stall prevention activation level

10-120%

120%

9-1

• r r

1

I I

_/

L L 1

11

Electronic thermal protection select

0: STD-motor, no soft stall

1: STD-motor, soft stall

2: VF-motor, no soft stall
3: VF-motot, soft stall

0

9-2

M n r

.

L'

.

1 r LI

USER GROUP PARAMETERS **

• /“

M

.

r I I

1

Maximum frequency

30 - 160 Hz

60 Hz

9-3

n L L

.

n

.

L LI

2

Automatic torque boost

0: Off

1: On

0

9-3

• / (

L LI

3

Torque boost

0 - 30 %

3%

9-3

• /

r 1

LI 1 L

4

Base frequency of maximum voltage level

25 - 160 Hz

60 Hz

9-3

1 1

(

n

.

L

_(

1

5

Standard setting mode selection

0: Factory settings

1: 50 Hz motor

2: 60 Hz motor
3: Reset to factory settings

0

9-3

n

r r

1

.

1 1 L L L

6

Acceleration time #2

0.1 - 1200 sec

10.0 sec

9-3

1 r

r

1

LI L L L

7

Deceleration time # 2

0.1 - 1200 sec

10.0 sec

9-3

n L 1

.1 L

.

1

8

Pattern of ACC/DEC #1

0: Linear

1: S-curve

2: C-curve

0

9-3

n

/

“1

.1 L

.

L

9

Pattern of ACC/DEC #2

0: Linear

1: S-Curve

2: C-Curve

1

9-4

•/“LI “1

_l

L L L

10

Selection to use ACC/DEC #1 or #2

0: Acc/Dec #1

1: Acc/Dec #2

0

9-4

n 1

• 1 L

11

V/F pattern

0: Constant torque

1: Variable torque

1

9-4

• L L r

r

. 1_1

,

L

- 1

12

Timed stop/coast to stop selection

0: Deceleration stop

1: Coast to stop

0

9-4

r 1 r

L LI LI L

13

Personal lock out code

0 - 255

0

9-4

7 - 2