background image

5.8 Terminal Connections and Functions (cont'd)

TOSHIBA

Terminal

name

Terminal functions

Terminal

location

ST

CC

(one of three)

SSI

JOG(SS2)

AD2(SS3)

RST

CC

(one of three)

Input terminal for run interlock. When ST is shorted to CC, the inverter
is ready to run. With ST-CC open the unit will not run and if opened

while running a coasting stop begins.

Input terminal for forward run. When F is shorted to CC, a forward
run starts. With F-CC open, the unit decelerates to a complete stop.

Input terminal for reverse run. When R is shorted to CC, a reverse run

starts. With R-CC open, the unit decelerates to a complete stop.

If terminals F-CC and R-CC are shorted simultaneously, a reverse

run occurs.

This is the common return for ST terminal.

Do not connect to GND(E).

Input terminal for multi-speed run frequencies. Depends on setting of

function [1 .tb], JOG/SS2 and AD2/SS3 terminals. (See Page 10-1)

Input terminal for jogging run or multi-speed run frequencies. Depends

on setting of function [l.tb], SSI, AD2(SS3) terminals. (See Page 10-1)

Input terminal for multispeed run frequencies. Depends on setting of

function [l.tb], SSI, JOG/SS2 terminals. (See Page 10-1)

With RST-CC shorted, the inverter's protective function resets.

This is the common return for ST, F, R, SSI, JOG(SS2), AD2(SS3),
and RST terminals. S

o

not connect to GND(E).

Control

PWB

terminal

block

GND(E)

(three provided)

The inverter earth ground terminal.

Do not connect to common return terminal (CC).

Frame

screw or

lug

R41/46

R40/44 *

R38

RJ *

R20/22

R10/11 *

T10/11 T20/22

Jumper to RJ when using 415V-50Hz/460V-60Hz incoming power.

Do not jumper to R40/44 or R38.

Jumper to RJ when using 400V-50Hz/440V-60Hz incoming power.

Do not jumper to R41/46 or R38.

Jumper to RJ when using 380V-50Hz incoming power.

Do not jumper to R41/46 or R40/44.

Common for input power selection. Jumper to either R41/46, R40/44,
or R38.

Do not jumper to more than one terminal at a time.

Output power terminal. Supplies 1-phase 200V-50Hz or 1-phase
220V-60HZ @ 40VA maximum.

Output power terminal. Supplies 1-phase 100V-50Hz or 1-phase

110V-60HZ @ 40VA maximum.

Output power return terminal for either 1-phase 200V-50Hz/220V-60Hz

@ 40VA or 1-phase 100V-50Hz/110V-60Hz @ 40VA.

Terminal

block

A

Supplied only on the Q2-4055 through Q2-420K units.

5 - 8