10.0 Input Terminal Operating Functions

Terminal operations are described as those operational features that can be controlled by

opening or closing relays (switches) across the terminal block (see Control/Driver Board Terminal

Block Details page 5-5). All of the functional combinations which can be accessed by terminal

control are discussed in this section. Remote operations from the terminals are possible even if

the inverter is in the manual control mode, however many of the terminals are multi-functional

(used for more than one function) and must be programmed for a particular application. Also

some of the terminals can be program disabled. Many of the operations that can be performed

by this inverter require program configuration and use of the terminals. Some of these functions

include Jog, Remote preset speeds. Remote meters. Outputting limit signals, and remote

start/stop.

10.1

Input Terminal Selection Function

The following chart shows all of the functional combinations for input terminal selection

function [l.tb]. See ITEM 5 page 7-3.

Input terminal

selection

parameter :1 .tb

Terminal Connection

Selected operating

frequency

AD2/SS3-CC

JOG/SS2-CC

SS1-CC

OFF

OFF

OFF

Operating frequency set via PP, IV, RR terminals

OFF

OFF

ON

1st speed operating frequency

OFF

ON

OFF

2nd speed operating frequency

0: SS2, SS3

OFF

ON

ON

3rd speed operating frequency

ON

OFF

OFF

4th speed operating frequency

ON

OFF

ON

5th speed operating frequency

ON

ON

OFF

6th speed operating frequency

ON

ON

ON

7th speed operating frequency

OFF

OFF

OFF

Operating frequency set via PP, IV, RR terminals

OFF

ON

OFF

Jogging run operating frequency

1: JOG, SS3

OFF

OFF

ON

1st speed operating frequency

ON

OFF

OFF

2nd speed operating frequency

ON

OFF

ON

3rd speed operating frequency

ON/OFF

OFF

OFF

Operating frequency set via PP, IV, RR terminals

2: SS2, AD2

ON/OFF

OFF

ON

1st speed operating frequency

ON/OFF

ON

OFF

2nd speed operating frequency

ON/OFF

ON

ON

3rd speed operating frequency

ON/OFF

OFF

OFF

Operating frequency set via PP, IV, RR terminals

3: JOG, AD2

ON/OFF

ON

OFF

Jogging run operating frequency

ON/OFF

OFF

ON

1st speed operating frequency

Note:

When function [l.tb] is set to 2 or 3 the [AD2] function is activated. This function enables

the user to remotely switch between the ACC/DEC patterns 1 and 2, provided [SEL2]=0.

If [SEL2]=1 then the only pattern available is given by [ACC2], [DEC2], or [Pt.2j. With

AD2-CC terminals shorted (ON) all ACC/DEC patterns are run using the settings of the

[ACC2], [DEC2], or [Pt.2] parameters.