10.5
Jog
The jogging frequency is immediately output when the remote JOG is activated. The
functions [JOG] and [J.StP] must be preset. In addition, the JOG(SS2) terminal must
be set for "JOG". This is accomplished by setting the function parameter [:l.tb] to 1 or 3.
The terminal connections are shown below:
Terminal Connections Required For Remote Jog
>-
o
z
UJ
O Hz
Terminal
inputs
Notes:
1)
A jogging run cannot be engaged by closing the JOG switch during a run.
2)
The inverter will decelerate at the selected rate during: deceleration stop, coast to stop, and DC
injection stop.
3)
F-CC must be broken for DC injection to be applied; breaking only JOG(SS2)-CC allows the
inverter to accept other input signals and is not a "true" off.
4)
See table on next page for terminal inputs and actions.
10.6
Resetting After a Trip
Pressing reset on the keypad resets the inverter faults. Momentarily closing a normally
open dry contact between terminals RST and COM resets the inverter faults remotely.
When the inverter trips due to an emergency stop or the activation of
one or more of its protective functions, the cause of the fauit must be
CAUTION
corrected before resetting the inverter. A forced restart with out prior
fauit correction measures couid damage the inverter and connected
devices.
1 0 - 3