Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual
Page 82

MODULEX EXT
1530, 1912, 2295, 2677, 3060 Boilers
Installation, Operation & Maintenance Manual
5.1 Installation Menu: Initializing the E8 Controller
Each time power is applied to the boiler and the E8 controller cover (Figure 5-1) is opened, the
INSTALLATION Menu is displayed once (only). These values MUST be entered in order to
initialize the boiler for operation. Once the values grouped here have been entered and
accepted, the controller is initiated and operatable and may be configured for your boiler
installation. To re-enter the
INSTALLATION menu, cycle the boiler power and open the cover
again.
To initialize the E8 Controller, set the following values in the
INSTALLATION Menu:
•
Set the parameters: ENGLISH, HOUR, YEAR, MONTH, and DAY.
•
Leave the BUS – ID HS parameter blank.
•
Remaining parameters are already set and do not require any entry.
Figure 5-1: INSTALLATION Menu
WARNING
Menu selections shown are
the factory default settings.
Refer to GF-115-C for the
complete menu selections.