3.22 Installation of the Exhaust and Air Intake System

NOTES

Consult local and state codes pertaining to special building code

and fire department requirements. Adhere to national code

requirements.
Observe the listed maximum lengths of vent system which are

boiler model dependent. The maximum permissible lengths are

listed in Section 3.23.

Minimum clearance of 4 ft. (1.22m) horizontally from, and in no case above or below, unless a 4 ft

(1.22 m) horizontal distance is maintained, from electric meters, gas meters, regulators and relief

equipment.
The minimum distance from adjacent public walkways, adjacent buildings, openable windows and

building openings shall not be less than those values specified in the National Fuel Gas Code,

ANI Z223.1 / NFPA 54 and/or the Natural Gas and Propabne Installation Code CAN/CSA B149.1.
Do not extend exposed vent pipe outside the building beyond recommended distance.

Condensate could freeze and block vent pipe.
Vent should terminate at least 3 ft (915 mm) away from adjacent walls, inside corners and 5 ft.

(1525 mm) below roof overhang (see Figure 3-16).
It is not recommended to terminate vent above any door or window, as condensate can freeze

causing ice formations.
Do not use a chimney as a raceway if another boiler or fireplace is vented into or through the

chimney.

Figure 3-16: Minimum Distances of Exhaust Opening and Building Features