3.33 Burner Calibration

WARNING!

All the instructions indicated below are for the exclusive use of

qualified AERCO service technicians or installers.

All the boilers are supplied already calibrated and tested. However, if it is necessary to change

the calibration due to gas conversion or adaptation to the mains supply system, the gas valve

must be re-calibrated (using

Service Mode function in the E8 controller).

3.33.1 Installing the Gas Analyzer Probe

Before making adjustments, a gas analyzer sensor probe must first be installed into the flue

exhaust outlet as shown in Figure 3-23, above.

Installing the Gas Analyzer Probe into Flue Outlet

1. Remove the cap (#2) from the gas outlet (#1)
2. Install the probe adapter (#3) into the gas outlet (#1) where cap was removed.
3. Insert the analysis probe (#4) into hole of the probe adaptor.
4. After measurements are taken and adjustments made, remove the probe, probe adaptor,

then reinstall the cap (#2) onto the gas outlet (#1).

Figure 3-27: Gas Analyzer Probe Location in Flue Outlet