10 other possible settings, 1 settings for heating circuit 1/2, 1 heating adjustment with constant flow temp – AERCO Modulex EXT 1530 - 3060 User Manual
Page 100: 2 temperature settings for heating circuits, Modulex ext

MODULEX EXT
1530, 1912, 2295, 2677, 3060 Boilers
Installation, Operation & Maintenance Manual
Table 5-6: EXPERT Menu - Continued
LEVEL
DESCRIPTION
ENTRY
HTG CIRCUIT 1/2
HC FUNCTION
Heating circuit function selection
0
(00 ÷ 04)
PUMP MODE
Pump operating mode
00
(00 ÷ 03)
MIXER OPEN
Open mixer dynamic
18
(5 ÷ 25)
MIXER CLOSE
Close mixer dynamic
12
(5 ÷ 25)
MAX T-FLOW
Max flow temperature setting
176
(68 ÷ 230)
MIN T-FLOW
Min flow temperature setting
10
(50 ÷ 230)
T-FROST PROT
Frost protection temperature
32
(5 ÷ 41)
OUT-TEMP-DEL
Ouside temperature delay
0
(0 ÷ 24)
SLOPE OFFSET
Heating slope distance
9
(0 ÷ 90)
B-HEAT SINK
Circuit enable
0
(00 ÷ 01)
RETURN
SOLAR / MF
RELAY FUNC 1 to 4
Function selection relay 1 to 4
0
(00 ÷ 26)
T-MF1 to 4 SETP
Switching temperature relay MF1 to 4
86
(86 ÷ 194)
MF 1 to 4 HYST
Hysteresys relay MF1 to 4
9
(4 ÷ 18)
FUNZ. F15
Sersor function F15
0
(00 ÷ 02)
RETURN
NOTE
There is another sub-menu under the EXPERT menu called
EXPERT HS. See section 3.35 – High Altitude Adjustment for
details.
NOTE
Some menus are visible only if the relevant sensor is wired.
5.10 Other Possible Settings
5.10.1 Settings for Heating Circuit 1/2
Heating Adjustment With Constant Flow Temp
5.10.1.1
(Without Outer Sensor)
Offers the possibility to have a constant flow temperature on the selected heating circuit.
•
INSTALLATION menu > HC FUNC “01”
Temperature Settings For Heating Circuits
5.10.1.2
(Only After Function Selection)
•
USER menu ⇒ Heating circuit I / II ⇒ FLOW TEMP DAY
•
USER menu ⇒ Heating circuit I / II ⇒ FLOW TEMP NIGHT
Page 100 of 138
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0095_0E
12/01/14
Phone: 800-526-0288
GF-139