38 controls and emergency functions, Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual
Page 70

MODULEX EXT
1530, 1912, 2295, 2677, 3060 Boilers
Installation, Operation & Maintenance Manual
3.38 Controls and Emergency Functions
Figure 3-34: MODULEX EXT Panel Controls and Indicators
ITEM
COMPONANT/FUNCTION
A
GLT (General Limit Thermostat): when enabled, it cuts the power supply to the
boiler and lights the warning lamp (Item D). To reset, remove the cap and push
the reset button.
B
Main Power Switch
C
Fuses: 1 = 6.3 A 2 = 10 A
D
Warning lamp of the Thermostatic
Lockout from GTL (General Limit Thermostat).
E
Main Switch
F*
Change-over Series/Parallel:
0 = Emergency is active or the control is managed by PLC or BMS.
I = Series connection (the cascade is managed by the BCM)
II = Parallel connection (condition of supply).
G*
In position “I” the plant will operate when requested at “CONSTANT SETPOINT”:
70°C –
Max heat output 50%.
H*
Enables burner reset in case of lock-out.
I*
YELLOW LED = Blinking = Communication between BMM and BCM is OK.
GREEN LED = ON = Active Pump
RED LED = ON = Failure Code Detected
*See section 4.2 for more information regarding the BCM (Boiler Communication Module).
NOTE
The emergency function enables the boiler’s burners to fire only at
50% and at 50°C in system return. All the system’s heating loads,
including the header pump, must be controlled manually.