36 high altitude conversion label, Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual

Page 68

background image

MODULEX EXT

1530, 1912, 2295, 2677, 3060 Boilers

Installation, Operation & Maintenance Manual

Table 3-7: MODULEX EXT FA (Factory) Parameters Set in PARAM HS xx Menu

Parameters

MODULEX EXT

For Low Altitude

For High Altitude

FAN MOD IGN

80

No Change

FAN MOD STBY

26

No Change

FAN MAX (FH)

84

100

FAN MIN (FL)

31

28

MAX DIFF PRO

30

No Change

MIN FLOW PRO

00

No Change

MIN FLOW RAT

200

No Change

BOIL HYS

5

No Change

BOIL SLP LIM

10

No Change

BOIL P VAL

25

No Change

BOIL I VAL

12

No Change

BOIL D VAL

00

No Change

PUMP OVERRUN

05

No Change

PUMP MIN MOD

----

----

CAP FLOW RATE

----

----

FAN P VAL

04

No Change

FAN I VAL

08

No Change

FAN SLP

FAN SLP POS

----

----

FAN SLP NEG

----

----

FAN START PW

----

----

FAN ADAPT

----

----

RESTARTS

----

----

SW NO

Software N°

Software N°

SW RWV

Software Revision

Software Revision

3.36 High Altitude Conversion Label

After calibration of the unit from Normal Altitude (0 - 2,000 feet) to High Altitude (2,000 –

4,500 feet) operation, the label below must be filled out with the appropriate information

and applied to the unit in close proximity to the rating label. If the unit is calibrated again

for normal altitude operation, the label should be removed.

Figure 3-32: High Altitude Conversion Label

Page 68 of 138

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0095_0E

12/01/14

Phone: 800-526-0288