beautypg.com

39 initial boiler ignition, 1 preliminary checks, Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual

Page 71

background image

MODULEX EXT

1530, 1912, 2295, 2677, 3060 BOILERS

Installation, Operation & Maintenance Manual

3.39 Initial Boiler Ignition

3.39.1 Preliminary Checks

CAUTION!

To ensure the continued safe operation of the boiler it is highly

recommended that it is checked at regular intervals and serviced

when necessary, and that only original spare parts are used.

Regular attention will prolong the life of the boiler.

Before igniting the boiler, check that:

The boiler installation has been carried out in accordance with the specific standards as

instructed in this manual.

The combustion air inlet and the discharge of combustion exhaust occur in the correct

manner in accordance to the specific standards in force.

The gas supply system is correctly configured for the boiler’s output.

The boiler’s electrical supply is 120 V - 60 Hz.

The system has been filled with water (pressure registered on the gauge 0.8/1 bar with

pump not running).

All of the system’s on/off valves are in the appropriate position (open or closed as required)

The mains gas supply corresponds to the one which the boiler has been calibrated for.

Otherwise convert the boiler to use the available gas (refer to section: “GAS

CONVERSION”). This operation must be carried out by a qualified technician in compliance

with the regulations in force.

The gas supply valve is open.

There are no gas leaks.

There are no water leaks.

The external mains electrical supply switch is on.

The boiler system’s safety valve is not blocked and is connected to the waste water system.

The condensate drain line has been filled with water and that it is connected to the waste

water system. (For more information, see section 3.14.)

WARNING!

Before firing up the appliance, be sure to fill up the condensate

drain line (see section 3.14) through the filling hole and check the

correct drainage of the condensate.
Using the boiler with the condensate drain siphon empty could

cause a dangerous condition due to poisonous emissions from the

flue exhaust gasses.

All the necessary ventilation conditions and minimum clearance distances are in place for

subsequent servicing in case the boiler is sited in a cupboard compartment.

There are no water leaks.

OMM-0095_0E

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 71 of 138

GF-139

Phone: 800-526-0288

12/01/14