MODULEX EXT

1530, 1912, 2295, 2677, 3060 Boilers

Installation, Operation & Maintenance Manual

3.15 Water Treatment

The chemical/physical composition of the heating system’s water is fundamental for the boiler’s

correct operation and safety.
Among the problems caused by poor quality of feed water, the most frequent and the most

serious is the buildup of deposits on boiler thermal exchange surfaces.
Less frequent, but also serious, are deposits on the water circulating piping surfaces. Because

of the low thermal conductivity of mineralization desposits caused by improperly treated water,

the thermal exchange efficiency may be seriously reduced, and can result in very dangerous

localized overheating.
AERCO suggests treating and conditioning feed water for the heating circuit in the following

cases:

When the hardness of the water is higher than 9 grains (15°f).

For cold/hot water installations with large water content.

Renewal of the water system due to uncontrolled leakages.

Subsequent refilling of the system due to maintenance work on the installation.

Presence of different metals in the water circuit.

Properly treated system and feed water will eliminate or substantially reduce the following

problems:

lime scale deposit

corrosion sludge

deposits

microbiological growths (molds, bacteria etc.)

An appropriate treatment of the supply water will prevent the above stated problems and will

maintain the correct operation and efficiency of the boiler over time.
In order to properly treat water for use in a hydronic boiler heating system, the following

physical/chemical characteristics must be addressed.
Water Hardness: If water hardness is over 6 to 9 grains, a water softener must be used.
Sediment: If sediment is present in the system, a sediment filter or other appropriate device,

must be used.
Water pH: If water has a pH above 8, or below 5, then the water must be treated to provide a

medium pH of between 5 and 8.
The system water to be judged for water characteristics should be taken from the return pipe of

the primary circuit downstream of the circulating pump.

3.16 Important Installation Warnings

3.16.1 Oxygen Levels in the System Water Warning

All necessary precautions must be taken for preventing the formation and localization of

oxygen in the system’s water. For this reason, ensure that the plastic piping used in

under-floor heating systems is impermeable to oxygen.

3.16.2 Antifreeze Compatibility Warning

If any anti-freeze solutions are used ensure that they are compatible with aluminum and

any other boiler components and materials.