32 testing the ignition safety shut-off device, Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual
Page 60

MODULEX EXT
1530, 1912, 2295, 2677, 3060 Boilers
Installation, Operation & Maintenance Manual
3.32 Testing the Ignition Safety Shut-off Device
Ignition Safety Shut-off Device Test
1. Power on by switching on the ON-OFF switch.
2. Create a request in C/H Central Heating using the E8 controller.
3. Turn burners ON.
4. Disconnect the igniter cable (WHITE) of BURNER 1 (See Figure 7-2).
NOTE
Ensure the cable end is not grounded to the enclosure frame, or to
any other grounded part.
5. The display will show Fault Code
E05 (Loss of Flame).
Figure 3-25: “Loss of Flame” FaultCode (E 05)
6. Press Reset Button on E8 Controller.
7. The boiler will retry the ignition cycle and the display will show Fault Code
E04 (No Flame
Detected During Ignition).
Figure 3-26: “No Flame Detected During Ignition” Fault Code (E 04)
8. Reconnect the ignition cable of BURNER 1.
9. Press Reset Button
10. Check that the boiler starts correctly.
WARNING!
Do not touch the inside of the ignition cable while it is disconnected
during start-up of the boiler.
Page 60 of 138
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0095_0E
12/01/14
Phone: 800-526-0288
GF-139