19 flue exhaust piping to vent, 20 vent starter pieces, Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual
Page 37

MODULEX EXT
1530, 1912, 2295, 2677, 3060 BOILERS
Installation, Operation & Maintenance Manual
3.19 Flue Exhaust Piping to Vent
In a condensing boiler the flue exhaust is evacuated at a very low temperature (maximum of
about 183°F / 84°C). Thus, it is necessary that the chimney be impermeble to the condensate of
the combustion products and be made of corrosion resistant materials.
The different joints must be well sealed and equipped with suitable gaskets in order to prevent
the escape of condensate and prevent the ingress of air.
To determine the proper cross section and height dimensions of the flue exhaust piping, refer to
national and local codes.
In order to prevent the formation of ice during the operation, the temperature of the internal wall
of the flue exhaust system should not be below 32 °F (0 °C) throughout its length.
For efficient venting of the combustion exhaust and to address condensation due to lower
external temperatures, ensure that combustion condensation is discharged into the boiler
condensate tray or into another separate collection pan according to the installation.
A test nipple, for measuring combustion gases, should be installed onto the first three feet of the
exhaust manifold flue. To do this, a hole with a diameter of 0.83‘‘ is drilled in a convenient
location for testing and the test nipple hardware assembled to the Flue pipe as shown in Figure
3-13.
Figure 3-13: Installation of Test Nipple into Flue Manifold Piping
NOTE
Damage caused by mistakes in installation, failure to complete the
instructions as written, or the improper use of the flue system are
not the responsibility of the supplier.
3.20 Vent Starter Pieces
All vent starter pieces for the Modulex EXT 1530 through 3060 can be purchased directly from
the vent manufacturer.
OMM-0095_0E
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 37 of 138
GF-139
Phone: 800-526-0288
12/01/14