Chapter 6 - Troubleshooting & Maintenance

92

fault contents to the memory in FU2-1 when the [RESET] key is pressed.

2) Fault History Contents
FU2-1~5 [Fault history] has the 5 most current faults in its memory. The smallest number will be the most
current fault in its memory. Check the operating information prior to fault.

Code Display

Description

FU2-1 Last

trip-1 Fault history 1

FU2-2 Last

trip-2 Fault history 2

FU2-3 Last

trip-3 Fault history 3

FU2-4 Last

trip-4 Fault history 4

FU2-5 Last

trip-5 Fault history 5


The FU2-6 [Erase Fault History] erases FU2-1~5 [Fault History] contents form the memory, and returns
the contents to the factory default status.

6.2 Fault (Inverter Fault) Reset


There are 3 ways to reset the inverter. The auto retry number will be initialized when the user resets the
inverter.

1) Reset by using the [STOP/RESET] key of the keypad.
2) Reset by shorting the RST-CM terminals on the control terminals.
3) Turn OFF the inverter and turn the inverter back ON.