Chapter 4 - Parameter Description [DRV]


35

DRV-03: Drive Mode (Run/stop Method)





Select the source of Run/Stop command.

Setting Range

Select Display

Description

Keypad

0

Run/stop is controlled by Keypad.

Fx/Rx-1

1

Control Terminals FX, RX and CM
control Run/Stop. (Method 1)

Fx/Rx-2

2

Control Terminals FX, RX and CM
control Run/Stop. (Method 2)

MODBUS-

RTU

3

Run/stop is controlled by Serial

Communication (MODBUS-RTU)
Refer to Chapter 5.














[Drive Mode: ‘Fx/Rx-1’]













[Drive Mode: ‘Fx/Rx-2’]

DRV-04: Frequency Mode (Frequency Setting
Method)





Select the source of frequency setting.

Setting Range

Select Display

Description

Keypad-1

0

Frequency is set at DRV-00. The

frequency is changed by pressing
[FUNC] key and entered by pressing
[FUNC] key. The inverter does not output

the changed frequency until the [FUNC]
key is pressed.

Keypad-2

1

Frequency is set at DRV-00. Press
[FUNC] key and then by pressing the
[▲], [▼] key, the inverter immediately

outputs the changed frequency. Pressing
the [FUNC] key saves the changed

frequency.

V1

2

Input the frequency reference (0-10V) to
the “V1” control terminal. Refer to the I/O-

01 to I/O-05 for scaling the signal.

I

3

Input the frequency reference (4~20mA)
to the “I” control terminal. Refer to the

I/O-06 to I/O-10 for scaling the signal.

V1+I

4

Input the frequency reference (0~10V,
4~20mA) to the “V1”,“I” control terminals.

The ‘V1’ signal overrides the ‘I’ signal.

MODBUS-

RTU

5

Frequency is set by Serial

Communication (MODBUS-RTU)
Refer to Chapter 5.














[Freq Mode: ‘V1’]

Output Frequency

FX-CM

Time

ON

RX-CM

ON

Forward

Reverse

Forward Run

Reverse Run

Output Frequency

FX-CM

Time

ON

RX-CM

ON

Forward

Reverse

Run/Stop

Direction

Output Frequency

Analog Signal
Input (V1)

Freq. Max

0V

10V

Reference Freq. Range

Related Functions: I/O-01 to I/O-10 [Reference Inputs]

I/O-01 to I/O-10: Scaling analog input signals (V1 and I) for

frequency reference.