Chapter 4 - Parameter Description [I/O]


65




















[Multi-Step Frequency Operation]





Note: The frequency for ‘Speed 0’ is determined by DRV-04.


[XCEL-L, XCEL-M, XCEL-H]
By setting P1, P2 and P3 terminals to ‘XCEL-L’,
‘XCEL-M’ and ‘XCEL-H’ respectively, up to 8
different Accel and Decel times can be used. The
Accel/Decel time is set in DRV-01 ~ DRV-02 and
I/O-25 ~ I/O-38.
The Accel/Decel time is determined by the
combination of P1, P2 and P3 terminals as shown
in the following table.

Accel/Decel

Time

Parameter

Code

XCEL-H

(P3)

XCEL-M

(P2)

XCEL-L

(P1)

Accel Time-0

DRV-01

Decel Time-0

DRV-02

0 0 0

Accel Time-1

I/O-25

Decel Time-1

I/O-26

0 0 1

Accel Time-2

I/O-27

Decel Time-2

I/O-28

0 1 0

Accel/Decel

Time

Parameter

Code

XCEL-H

(P3)

XCEL-M

(P2)

XCEL-L

(P1)

Accel Time-3

I/O-29

Decel Time-3

I/O-30

0 1 1

Accel Time-4

I/O-31

Decel Time-4

I/O-32

1 0 0

Accel Time-5

I/O-34

Decel Time-5

I/O-35

1 0 1

Accel Time-6

I/O-36

Decel Time-6

I/O-37

1 1 0

Accel Time-7

I/O-38

Decel Time-7

I/O-39

1 1 1

0: OFF, 1: ON















[Multi-Accel/Decel Time Operation]




[DC-Brake]
DC Injection Braking can be activated during
inverter stopped by configuring one of the multi-
function input terminals (P1, P2, P3) to ‘DC-Bake’.
To activate the DC Injection Braking, close the
contact on the assigned terminal while the inverter
is stopped.

[2

nd

Function]

Inverter uses parameters set in FU2-81 ~ 89
when this terminal is ON. This function must be
used when motor is stopped to avoid over current

P1-CM

ON

ON

Output Frequency

Time

Time

P2-CM

ON

ON

Time

P3-CM

ON

Time

JOG-CM

ON

Time

FX-CM

ON

Time

RX-CM

ON

Time

ON

ON

Step

0

Step

1

Step

2

Step

3

Step

4

Step

5

Step

6

Step

7

Jog

Related Functions: DRV-05 ~ DRV-07 [Step Frequency]

I/O-20 [Jog Frequency]

I/O-21 ~ I/O-24 [Step Frequency]

P1-CM

ON

Output Frequency

Time

Time

P2-CM

ON

Time

P3-CM

ON

Time

FX-CM

ON

Time

ON

ON

ON

ON

Ref.

Freq.

Time 0 Time 1 Time 2 Time 3 Time 4 Time 5 Time 6 Time 7

Related Functions: I/O-25 ~ I/O-38 [1

st

~7

th

Accel/Decel Time]