Cleveland Range inverter User Manual
Page 35

Chapter 3 - Parameter List
29
Code
Description
Keypad
Display
Setting Range
Units
Factory
Default
Adj.
During
Run
Page
3 (Drv Mode)
4 (Freq Mode)
5 (Step Freq 1)
6 (Step Freq 2)
7 (Step Freq 3)
8 (Current)
9 (Speed)
10(DC Link Vtg)
11 (User Display)
12 (Fault Display)
13 (Motor Direction)
0 (Voltage)
1 (Watt)
FU2-73 User Display Selection
H 73
2 (Torque)
-
0 (Voltage)
Yes 58
FU2-74 Gain for Motor Speed Display
H 74
1 to 1000 [%]
1
100 [%]
Yes
58
0 (None)
1 (None)
FU2-75
DB (Dynamic Braking) Resistor Mode
Selection
H 75
2 (Ext. DB-R)
-
2 (Ext. DB-R) Yes 59
FU2-76 Duty of Dynamic Braking Resistor
H 76
0 to 30 [%]
1
10 [%]
Yes
59
FU2-79 Software Version
H 79
.
-
.
-
59
FU2-81
17
2
nd
Acceleration Time
H 81
0.0 to 999.9 [sec]
0.1
5.0 [sec]
Yes
FU2-82 2
nd
Deceleration Time
H 82
0.0 to 999.9 [sec]
0.1
10.0 [sec]
Yes
FU2-83 2
nd
Base Frequency
H 83
30 to FU1-20
0.01
50 / 60 [Hz]
No
0 (Linear)
1 (Square)
FU2-84 2
nd
V/F Pattern
H 84
2 (User V/F)
-
0 (Linear)
No
FU2-85 2
nd
Forward Torque Boost
H 85
0 to 15 [%]
0.1
2.0 [%]
No
FU2-86 2
nd
Reverse Torque Boost
H 86
0 to 15 [%]
0.1
2.0 [%]
No
FU2-87 2
nd
Stall Prevention Level
H 87
30 to 250 [%]
1
200[%]
No
FU2-88
2
nd
Electronic Thermal Level for 1
Minute
H 88
FU2-89 to 250 [%]
1 180
[%]
Yes
FU2-89
2
nd
Electronic Thermal Level for
Continuous
H 89
50 to (FU2-88)
1 120
[%]
Yes
FU2-90 2
nd
Rated Motor Current
H 90
0.1 to 99.9 [A]
0.1
- [A]
No
59
0 (No)
FU2-91
Read Parameters into Keypad from
Inverter
H 91
1 (Yes)
-
0 (No)
No
0 (No)
FU2-92
Write Parameters to Inverter from
Keypad
H 92
1 (Yes)
-
0 (No)
No
60
17