Chapter 4 - Parameter Description [I/O]


71

[OL]
MO-MG is CLOSED when the output current has
reached the FU1-54 [Overload Warning Level] for
the FU1-55 [Overload Warning Time].













[MO-MG configured as ‘OL’]





[IOL]
MO-MG is CLOSED when the output current is
above the 150% of rated inverter current for 36
seconds. If this situation is continued for one
minute, the inverter will cut off its output and
displays ‘IOLT’ (Inverter overload trip). See the
nameplate for the rated inverter current.












[MO-MG configured as ‘IOL’]

[Stall]
MO-MG is CLOSED when the inverter is on the
stall prevention mode.















[MO-MG configured as ‘Stall’]





[OV]
MO-MG is CLOSED when the DC link voltage is
above the Over-voltage level.










[MO-MG configured as ‘OV’]


Related Functions: FU1-54 [Overload Warning Level]

FU1-55 [Overload Warning Time]

t1: FU1-55 [Overload Warning Time]

Output Current

Time

Time

FU1-54

[OL level]

FU1-54

[OL level]

MO-MG

ON

t1

t1

Output Current

Time

Time

150% of Rated

Inverter Current

MO-MG

ON

36sec

150% of Rated

Inverter Current

24sec

Output Current

Time

Output Frequency

Time

FU1-60

[Stall Level]

FU1-60

[Stall Level]

Time

CLOSED

MO-MG

Related Functions: FU1-59 [Stall Prevention Mode]

FU1-60 [Stall Prevention Level]

MO-MG

ON

DC Link Voltage

Time

Time

OV Level (380V DC or 760V DC)