2 function group 1 [fu1 – Cleveland Range inverter User Manual
Page 31

Chapter 3 - Parameter List
25
3.2 Function Group 1 [FU1]
Code
Description
Keypad
Display
Setting Range
Units
Factory
Default
Adj.
During
Run
Page
FU1-00 Jump to Desired Code #
F 0
1 to 99
1
3
Yes
39
0 (None)
1 (Forward Prev)
FU1-03 Run Prevention
F 3
2 (Reverse Prev)
-
0 (None)
No
39
0 (Linear)
1 (S-Curve)
2 (U-Curve)
3 (Minimum)
FU1-05 Acceleration Pattern
F 5
4 (Optimum)
-
0 (Linear)
No
39
0 (Linear)
1 (S-Curve)
2 (U-Curve)
3 (Minimum)
FU1-06 Deceleration Pattern
F 6
4 (Optimum)
-
0 (Linear)
No
39
0 (Decel)
1 (DC-Brake)
FU1-07 Stop Mode
F 7
2 (Free-Run)
-
0 (Decel)
No
40
FU1-08
7
DC Injection Braking Frequency
F 8
(FU1-22) to 50/60 [Hz]
0.01
5.00 [Hz]
No
FU1-09 DC Injection Braking On-delay Time
F 9
0 to 60 [sec]
0.01
0.10 [sec]
No
FU1-10 DC Injection Braking Voltage
F 10
0 to 200 [%]
1
50 [%]
No
FU1-11 DC Injection Braking Time
F 11
0 to 60 [sec]
0.1
1.0 [sec]
No
41
FU1-12
Starting DC Injection Braking
Voltage
F 12
0 to 200 [%]
1
50 [%]
No
FU1-13 Starting DC Injection Braking Time
F 13
0.0 to 60.0 [sec]
0.1
0.0 [sec]
No
41
FU1-20 Maximum Frequency
F 20
40.00 to 400.00 [Hz]
0.01
50 / 60 [Hz]
No
FU1-21 Base Frequency
F 21
30.00 to (FU1-20)
0.01
50 / 60 [Hz]
No
FU1-22 Starting Frequency
F 22
0.10 to 10.00 [Hz]
0.01 0.10
[Hz] No
42
0 (No)
FU1-23 Frequency Limit Selection
F 23
1 (Yes)
-
0 (No)
No
FU1-24
8
Low Limit Frequency
F 24
0.00 to (FU1-25)
0.01 0.00
[Hz] No
FU1-25 High Limit Frequency
F 25
(FU1-24) to (FU1-20)
0.01
50 / 60 [Hz]
No
42
0 (Manual)
FU1-26
Manual/Auto Torque Boost
Selection
F 26
1 (Auto)
-
0 (Manual)
No
FU1-27 Torque Boost in Forward Direction
F 27
0.1 2.0
[%] No
FU1-28 Torque Boost in Reverse Direction
F 28
0.0 to 15.0 [%]
0.1 2.0
[%] No
43
7
Code FU1-08 through FU1-11 appears only when FU1-07 is set to ‘DC-brake’.
8
Code FU1-24 through FU1-25 appears only when FU1-23 is set to ‘Yes’.