Chapter 5 - MODBUS-RTU Communication
76
5.4 Operating
5.4.1 Operating
Steps
- Check whether the computer and the inverter are connected correctly.
- Turn ON the inverter. But, do not connect the load until stable communication between the computer
and the inverter is verified.
- Start the operating program for the inverter from the computer.
- Operate the inverter using the operating program for the inverter.
- Refer to “6. Troubleshooting” if the communication is not operating normally.
User program or the “DriveView” program supplied from CMC Industrial Systems can be used as the
operating program for the inverter if I/O-50 [Communication Protocol Selection] was set to default
value 0.
5.5 Communication Protocol (Modbus-RTU)
The communication structure is that the ACtionMaster drives are slaves and a computer/host is the
master.
5.5.1 Supported Function Code
Function Code
Name
0x03
Read Hold Register
0x04
Read Input Register
0x06
Preset Single Register
0x10
Preset Multiple Register
5.5.2 Exception
Code
Exception Code
Name
0x01
ILLEGAL FUNCTION
0x02
ILLEGAL DATA ADDRESS
0x03
ILLEGAL DATA VALUE
0x06
SLAVE DEVICE BUSY
5.5.3 Baud
Rate
1200, 2400, 4800, 9600, 19200bps (default value of 9600bps)