Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages

with Troubleshooting Guides (cont)

L. CHILLER PROTECT LIMIT FAULTS (cont)

Excessive numbers of the same fault can lead to severe chiller
damage. Seek service expertise.

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

PROTECTIVE LIMIT

TRANSDUCER VOLTAGE FAULT

V

REF [VALUE] exceeded limit of [LIMIT]*.

Check transducer power supply.

Check transformer power (5 vdc) supply to
transducers. Power must be 4.5 to 5.5 vdc.

PROTECTIVE LIMIT

LOW GEAR OIL PRESSURE

GEAROILP [VALUE] exceeded imit of
[LIMIT]*. Check gear oil pump filter.

Check for closed oil supply valves. Check oil fil-
ter. Check transducer accuracy.

PROTECTIVE LIMIT

HIGH GEAR OIL TEMP

GEAOILT [VALUE] exceeded limit of
[LIMIT]*. Check gear oil cooler filter.

Check for cooler water flow. Check sensor for
accuracy.

PROTECTIVE LIMIT

CCN OVERRIDE STOP

CHIL

S

S CCN. Override stop while in

local run mode.

Machine received a command from the net-
work to stop overriding local operating mode.

*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by

the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage,
etc., at which the control tripped. [OPEN] indicates that an input circuit is open.

M. CHILLER ALERTS

PRIMARY MESSAGE

SECONDARY MESSAGE

ALARM MESSAGE/PRIMARY CAUSE

ADDITIONAL CAUSE/REMEDY

RECYCLE ALERT

HIGH AMPS AT SHUTDOWN

High Amps at Recycle: Check guide vane
drive.

Check that guide vanes are closing. Check
motor amps correction calibration is cor-
rect. Check actuator for proper operation.

SENSOR FAULT ALERT

LEAVING COND WATER TEMP

Sensor Fault: Check leaving condenser
water sensor.

Check sensor. See sensor test procedure.

SENSOR FAULT ALERT

ENTERING COND WATER TEMP

Sensor Fault: Check entering condenser
water sensor.

LOW OIL PRESSURE
ALERT

CHECK OIL FILTER

Low Oil Pressure Alert: Check oil

Check oil filter. Check for improper oil level
or temperature.

AUTORESTART PENDING

POWER LOSS

V

P Power Loss: Check voltage

supply.

Check power supply if there are excessive
compressor starts occurring.

AUTORESTART PENDING

LOW LINE VOLTAGE

V

P [VALUE] exceeded limit of [LIMIT]*.

Check voltage supply.

AUTORESTART PENDING

HIGH LINE VOLTAGE

V

P [VALUE] exceeded limit of [LIMIT]*.

Check voltage supply.

SENSOR ALERT

HIGH DISCHARGE TEMP

CMPD [VALUE] exceeded limit of
[LIMIT]*. Check discharge
temperature.

Discharge temperature exceeded the alert
threshold. Check entering condenser water
temperature.

SENSOR ALERT

HIGH BEARING TEMP

MTRB [VALUE] exceeded limit of
[LIMIT]*. Check thrust bearing
temperature.

Thrust bearing temperature exceeded the
alert threshold. Check for closed valves, im-
proper oil level or temperatures.

CONDENSER PRESSURE
ALERT

PUMP RELAY ENERGIZED

CRP High Condenser Pressure [LIMIT]*.
Pump energized to reduce pressure.

Check ambient conditions. Check con-
denser pressure for accuracy.

RECYCLE ALERT

EXCESSIVE RECYCLE STARTS

Excessive recycle starts.

The chiller load is too small to keep the chiller
on line and there have been more than 5
restarts in 4 hours. Increase chiller load, ad-
just hot gas bypass, increase

RECYCLE RE-

START DELTA T

from SERVICE1 screen.

SENSOR ALERT

LOW GEAR OIL PRESSURE

GEAROILP [VALUE] exceeded imit of
[LIMIT]*. Check gear oil pump filter.

Check for closed oil supply valves. Check
oil filter. Check transducer accuracy.

SENSOR ALERT

HIGH GEAR OIL TEMP

GEAOILT [VALUE] exceeded limit of
[LIMIT]*. Check gear oil cooler filter.

Check for cooler water flow. Check sensor
for accuracy.

*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by

the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage,
etc., at which the control tripped.