Table 16 — additional cooler weights – Carrier 17EX User Manual

Page 100

background image

Table 15 — 17EX Heat Exchanger Economizer/Storage Vessel, Piping, and Pumpout Unit Weights*

COOLER

SIZE†

COOLER

TOTAL

WEIGHT

COOLER
CHARGE

ECONOMIZER/

STORAGE

VESSEL

ECONOMIZER

REFRIGERANT

MISCELLANEOUS

PIPING

PUMPOUT

UNIT

Dry**

Operating††

Refrigerant

Water

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

gal

kg

L

45

25,032

11 355

30,098

13 652

2,060

934

3,006

361

1 364

1366

7,900

3 583

840

318

1,149

521

210

95

46

25,529

11 580

30,881

14 008

2,160

980

3,192

383

1 448

1450

47

26,025

11 805

31,663

14 362

2,260

1 025

3,378

405

1 532

1533

48

28,153

12 770

34,866

15 815

2,540

1 152

4,173

500

1 893

1893

CONDENSER

SIZE†

CONDENSER TOTAL WEIGHT

CONDENSER CHARGE

Dry**

Operating††

Refrigerant

Water

lb

kg

lb

kg

lb

kg

lb

kg

45

16,676

7 564

20,596

9 342

1,200

544

2,720

1 234

46

17,172

7 789

21,280

9 653

1,200

544

2,908

1 319

47

17,669

8 015

21,965

9 963

1,200

544

3,096

1 404

55

20,725

9 401

25,598

11 611

1,420

644

3,453

1 566

56

21,663

9 826

26,891

12 198

1,420

644

3,808

1 727

57

22,446

10 182

27,971

12 688

1,420

644

4,105

1 862

*If a chiller configuration other than 2-pass, 150 psig (1034 kPa), NIH waterbox

configuration is used, refer to Tables 16 and 17 to obtain the additional dry and
water weights that must be added to the values shown in this table.

†Cooler and condenser weights shown are based on 2-pass, nozzle-in-head

(NIH) waterboxes with 150 psig (1034 kPa) covers. Includes components at-
tached to cooler, but does not include suction/discharge, elbow, or other
interconnecting piping.

**Dry weight includes all components attached to economizer: covers, float valves,

brackets, control center (31 lb [14 kg]), and power panel (20 lb [9 kg]). Dry
weight does not include compressor weight, motor weight, or pumpout con-
densing unit weight. The pumpout condensing unit weight is 210 lb (95 kg).
For compressor and motor weights, refer to Tables 18 and 20A and 20B.

††Operating weight includes dry weight, refrigerant weight, and water weight.

Table 16 — Additional Cooler Weights*

COOLER

FRAME

WATERBOX

TYPE

NUMBER

OF PASSES

DESIGN MAXIMUM

WATER PRESSURE

ADDITIONAL

DRY WEIGHT

ADDITIONAL

WATER WEIGHT

psig

kPa

lb

kg

lb

gal

kg

L

4

NIH

1, 3

150

1034

515

234

NIH

1, 3

300

2068

2941

1334

NIH

2

300

2068

2085

946

Marine

1, 3

150

1034

2100

953

5102

612

2314

2314

Marine

2

150

1034

792

359

2551

306

1157

1157

Marine

1, 3

300

2068

3844

1744

5102

612

2314

2314

Marine

2

300

2068

2536

1150

2551

306

1157

1157

*When using a chiller configuration other than 2-pass, NIH waterboxes with 150 psig (1038 kPa) covers, add the weighs listed in this table to the

appropriate weights in Table 15 to obtain the correct cooler weight.

Fig. 56 — Model Number Nomenclature for Compressor Size (See Fig. 1 Also)

100