Table 15 — 17EX Heat Exchanger Economizer/Storage Vessel, Piping, and Pumpout Unit Weights*
COOLER
SIZE†
COOLER
TOTAL
WEIGHT
COOLER
CHARGE
ECONOMIZER/
STORAGE
VESSEL
ECONOMIZER
REFRIGERANT
MISCELLANEOUS
PIPING
PUMPOUT
UNIT
Dry**
Operating††
Refrigerant
Water
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
kg
lb
gal
kg
L
45
25,032
11 355
30,098
13 652
2,060
934
3,006
361
1 364
1366
7,900
3 583
840
318
1,149
521
210
95
46
25,529
11 580
30,881
14 008
2,160
980
3,192
383
1 448
1450
47
26,025
11 805
31,663
14 362
2,260
1 025
3,378
405
1 532
1533
48
28,153
12 770
34,866
15 815
2,540
1 152
4,173
500
1 893
1893
CONDENSER
SIZE†
CONDENSER TOTAL WEIGHT
CONDENSER CHARGE
Dry**
Operating††
Refrigerant
Water
lb
kg
lb
kg
lb
kg
lb
kg
45
16,676
7 564
20,596
9 342
1,200
544
2,720
1 234
46
17,172
7 789
21,280
9 653
1,200
544
2,908
1 319
47
17,669
8 015
21,965
9 963
1,200
544
3,096
1 404
55
20,725
9 401
25,598
11 611
1,420
644
3,453
1 566
56
21,663
9 826
26,891
12 198
1,420
644
3,808
1 727
57
22,446
10 182
27,971
12 688
1,420
644
4,105
1 862
*If a chiller configuration other than 2-pass, 150 psig (1034 kPa), NIH waterbox
configuration is used, refer to Tables 16 and 17 to obtain the additional dry and
water weights that must be added to the values shown in this table.
†Cooler and condenser weights shown are based on 2-pass, nozzle-in-head
(NIH) waterboxes with 150 psig (1034 kPa) covers. Includes components at-
tached to cooler, but does not include suction/discharge, elbow, or other
interconnecting piping.
**Dry weight includes all components attached to economizer: covers, float valves,
brackets, control center (31 lb [14 kg]), and power panel (20 lb [9 kg]). Dry
weight does not include compressor weight, motor weight, or pumpout con-
densing unit weight. The pumpout condensing unit weight is 210 lb (95 kg).
For compressor and motor weights, refer to Tables 18 and 20A and 20B.
††Operating weight includes dry weight, refrigerant weight, and water weight.
Table 16 — Additional Cooler Weights*
COOLER
FRAME
WATERBOX
TYPE
NUMBER
OF PASSES
DESIGN MAXIMUM
WATER PRESSURE
ADDITIONAL
DRY WEIGHT
ADDITIONAL
WATER WEIGHT
psig
kPa
lb
kg
lb
gal
kg
L
4
NIH
1, 3
150
1034
515
234
—
—
—
—
NIH
1, 3
300
2068
2941
1334
—
—
—
—
NIH
2
300
2068
2085
946
—
—
—
—
Marine
1, 3
150
1034
2100
953
5102
612
2314
2314
Marine
2
150
1034
792
359
2551
306
1157
1157
Marine
1, 3
300
2068
3844
1744
5102
612
2314
2314
Marine
2
300
2068
2536
1150
2551
306
1157
1157
*When using a chiller configuration other than 2-pass, NIH waterboxes with 150 psig (1038 kPa) covers, add the weighs listed in this table to the
appropriate weights in Table 15 to obtain the correct cooler weight.