Table 2 — LID Display Data (cont)

EXAMPLE 7 — LEAD/LAG CONFIGURATION DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press SERVICE .

3. Scroll down to highlight EQUIPMENT CONFIGURATION.

4. Press SELECT .

5. Scroll down to highlight LEAD/LAG.

6. Press SELECT .

LEAD/LAG CONFIGURATION SCREEN

DESCRIPTION

CONFIGURABLE RANGE

UNITS

REFERENCE POINT NAME

DEFAULT VALUE

LEAD/LAG SELECT

DISABLE =0, LEAD =1,
LAG =2, STANDBY =3

0-3

leadlag

0

Load Balance Option

DISABLE/ENABLE

loadbal

DISABLE

Common Sensor Option

DISABLE/ENABLE

commsens

DISABLE

LAG Percent Capacity

25-75

%

lag

per

50

LAG Address

1-236

lag

add

92

LAG START Timer

2-60

MIN

lagstart

10

LAG STOP Timer

2-60

MIN

lagstop

10

PRESTART FAULT Timer

0-30

MIN

preflt

5

STANDBY Chiller Option

DISABLE/ENABLE

stndopt

DISABLE

STANDBY Percent Capacity

25-75

%

stnd

per

50

STANDBY Address

1-236

stnd

add

93