Table 2 — LID Display Data (cont)

EXAMPLE 2 — STATUS02 DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press STATUS .

3. Scroll down to highlight STATUS02.

4. Press SELECT .

DESCRIPTION

POINT TYPE

UNITS

REFERENCE POINT NAME

(ALARM HISTORY)

INPUT

OUTPUT

Hot Gas Bypass Relay

X

OFF/ON

HGBR

*Chilled Water Pump

X

OFF/ON

CHWP

Chilled Water Flow

X

NO/YES

EVFL

*Condenser Water Pump

X

OFF/ON

CDP

Condenser Water Flow

X

NO/YES

CDFL

Compressor Start Relay

X

OFF/ON

CMPR

Compressor Start Contact

X

OPEN/CLOSED

1CR

AUX

Compressor Run Contact

X

OPEN/CLOSED

RUN

AUX

Starter Fault Contact

X

OPEN/CLOSED

STR

FLT

Pressure Trip Contact

X

OPEN/CLOSED

PRS

TRIP

Single Cycle Dropout

X

NORMAL/ALARM

V1

CYCLE

Oil Pump Relay

X

OFF/ON

OILR

Oil Heater Relay

X

OFF/ON

OILH

Motor Cooling Relay†

X

OFF/ON

MTRC

Auxiliary Oil Pump Relay

X

OFF/ON

AUXOILR

*Tower Fan Relay

X

OFF/ON

TFR

Compr. Shunt Trip Relay

X

OFF/ON

TRIPR

Alarm Relay

X

NORMAL/ALARM

ALM

Spare Prot Limit Input

X

ALARM/NORMAL

SPR

PL

†Information is applicable to hermetic machines only.

NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).

EXAMPLE 3 — STATUS03 DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press STATUS .

3. Scroll down to highlight STATUS03.

4. Press SELECT .

DESCRIPTION

RANGE

UNITS

REFERENCE POINT NAME

(ALARM HISTORY)

OPTIONS BOARD 1
*Demand Limit 4-20 mA

4-20

mA

DEM

OPT

*Temp Reset 4-20 mA

4-20

mA

RES

OPT

*Common CHWS Sensor

–40-245 (–40-118)

DEG F (DEG C)

CHWS

*Common CHWR Sensor

–40-245 (–40-118)

DEG F (DEG C)

CHWR

*Remote Reset Sensor

–40-245 (–40-118)

DEG F (DEG C)

R

RESET

*Temp Sensor — Spare 1

–40-245 (–40-118)

DEG F (DEG C)

SPARE1

*Temp Sensor — Spare 2

–40-245 (–40-118)

DEG F (DEG C)

SPARE2

*Temp Sensor — Spare 3

–40-245 (–40-118)

DEG F (DEG C)

SPARE3

OPTIONS BOARD 2
*4-20 mA — Spare 1

4-20

mA

SPARE1

M

*4-20 mA — Spare 2

4-20

mA

SPARE2

M

*Temp Sensor — Spare 4

–40-245 (–40-118)

DEG F (DEG C)

SPARE4

*Temp Sensor — Spare 5

–40-245 (–40-118)

DEG F (DEG C)

SPARE5

*Temp Sensor — Spare 6

–40-245 (–40-118)

DEG F (DEG C)

SPARE6

*Temp Sensor — Spare 7

–40-245 (–40-118)

DEG F (DEG C)

SPARE7

*Temp Sensor — Spare 8

–40-245 (–40-118)

DEG F (DEG C)

SPARE8

*Temp Sensor — Spare 9

–40-245 (–40-118)

DEG F (DEG C)

SPARE9

NOTE: values preceded by an asterisk (*) can be forced (changed by an operator) from the LID screen
or from another control device (such as a Carrier Comfort Network [CCN] terminal).