LEGEND FOR TABLE 12, A - N
1CR
AUX
— Compressor Start Contact
CA
P
— Compressor Current
CCN
— Carrier Comfort Network
CDFL
— Condenser Water Flow
CHIL
S
S — Chiller Start/Stop
CHW
— Chilled Water
CMPD
— Discharge Temperature
CRP
— Condenser Pressure
ERT
— Evaporator Refrigerant Temperature
EVFL
— Chilled Water Flow
GV
TRG
— Target Guide Vane Position
LED
— Light-Emitting Diode
LID
— Local Interface Device
MTRB
— Bearing Temperature
MTRW
— Motor Winding Temperature
OILPD
— Oil Pressure
OILT
— Oil Sump Temperature
PIC
— Product Integrated Control
PRS
TRIP — Pressure Trip Contact
PSIO
— Processor Sensor Input/Output Module
RLA
— Rated Load Amps
RUN
AUX — Compressor Run Contact
SMM
— Starter Management Module
SPR
PL
— Spare Protective Limit Input
STR
FLT
— Starter Fault
TXV
— Thermostatic Expansion Valve
V
P
— Line Voltage: Percent
V
REF
— Voltage Reference
Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
A. SHUTDOWN WITH ON/OFF/RESET-OFF
PRIMARY MESSAGE
SECONDARY MESSAGE
PROBABLE CAUSE/REMEDY
MANUALLY STOPPED — PRESS
CCN OR LOCAL TO START
PIC in OFF mode, press the CCN or local softkey to
start unit.
TERMINATE PUMPDOWN MODE
TO SELECT CCN OR LOCAL
Enter the CONTROL TEST table and select
TERMINATE LOCKOUT
to unlock compressor.
SHUTDOWN IN PROGRESS
COMPRESSOR UNLOADING
Chiller unloading before shutdown due to soft/stop feature.
SHUTDOWN IN PROGRESS
COMPRESSOR DEENERGIZED
Chiller compressor is being commanded to stop. Water pumps are deen-
ergized within one minute.
ICE BUILD
OPERATION COMPLETE
Chiller shutdown from Ice Build operation.
B. TIMING OUT OR TIMED OUT
PRIMARY MESSAGE
SECONDARY MESSAGE
PROBABLE CAUSE/REMEDY
READY TO START IN XX MIN
UNOCCUPIED MODE
Time schedule for PIC is unoccupied.
Chillers will start only when occupied.
READY TO START IN XX MIN
REMOTE CONTACTS OPEN
Remote contacts have stopped chiller. Close contacts to start.
READY TO START IN XX MIN
STOP COMMAND IN EFFECT
Chiller START/STOP on STATUS01 manually forced to stop. Re-
lease value to start.
READY TO START IN XX MIN
RECYCLE RESTART PENDING
Chiller in recycle mode.
READY TO START
UNOCCUPIED MODE
Time schedule for PIC is unoccupied. Chiller will start when occu-
pied. Make sure the time and date have been set on the
SERVICE menu.
READY TO START
REMOTE CONTACTS OPEN
Remote contacts have stopped chiller. Close contacts to start.
READY TO START
STOP COMMAND IN EFFECT
Chiller START/STOP on STATUS01 manually forced to stop. Re-
lease value to start.
READY TO START IN XX MIN
REMOTE CONTACTS CLOSED
Chiller timer counting down unit. Ready for start.
READY TO START IN XX MIN
OCCUPIED MODE
Chiller timer counting down unit. Ready for start.
READY TO START
REMOTE CONTACTS CLOSED
Chiller timers complete, unit start will commence.
READY TO START
OCCUPIED MODE
Chiller timers complete, unit start will commence.
STARTUP INHIBITED
LOADSHED IN EFFECT
CCN loadshed module commanding chiller to stop.
READY TO START IN XX MIN
START COMMAND IN EFFECT
Chiller START/STOP on STATUS01 has been manually forced to
start. Chiller will start regardless of time schedule or remote contact
status.
C. IN RECYCLE SHUTDOWN
PRIMARY MESSAGE
SECONDARY MESSAGE
PROBABLE CAUSE/REMEDY
RECYCLE RESTART PENDING
OCCUPIED MODE
Unit in recycle mode, chilled water temperature is not high enough
to start.
RECYCLE RESTART PENDING
REMOTE CONTACT CLOSED
Unit in recycle mode, chilled water temperature is not high enough
to start.
RECYCLE RESTART PENDING
START COMMAND IN EFFECT
Chiller START/STOP on STATUS01 manually forced to start, chilled
water temperature is not high enough to start.
RECYCLE RESTART PENDING
ICE BUILD MODE
Chiller in ICE BUILD mode. Chilled water/brine temperature is satis-
fied for
ICE BUILD SETPOINT
temperature.