Table 2 — LID Display Data (cont)

EXAMPLE 4 — STATUS04 DISPLAY SCREEN

To access this display from the LID default screen:
1. Press

MENU

.

2. Press STATUS .

3. Scroll down to highlight STATUS04.

4. Press SELECT .

DESCRIPTION

RANGE

UNITS

REFERENCE POINT NAME

(ALARM HISTORY)

Main Gear Oil Pump

OFF/ON

MAINPMP1

Auxiliary Gear Oil Pump

OFF/ON

AUXPMP2

Gear Oil Pressure

−6.7 to 420 (−46 to 2896)

psi (kPa)

GEAROILP

Gear Oil Temperature

−40 to 245 (−40 to 118)

DEG F (DEG C)

GEAROILT

EXAMPLE 5 — SETPOINT DISPLAY SCREEN

To access this display from the LID default screen:

1. Press

MENU

.

2. Press SETPOINT .

DESCRIPTION

CONFIGURABLE RANGE

UNITS

REFERENCE POINT NAME

DEFAULT VALUE

Base Demand Limit

40-100

%

DLM

100

LCW Setpoint

20-120 (–6.7-48.9)

DEG F (DEG C)

lcw

sp

50.0 (10.0)

ECW Setpoint

20-120 (–6.7-48.9)

DEG F (DEG C)

ecw

sp

60.0 (15.6)

ICE BUILD Setpoint

20- 60 (–6.7-15.6)

DEG F (DEG C)

ice

sp

40.0 ( 4.4)

25