beautypg.com

Carrier 17EX User Manual

Page 18

background image

3. Press SELECT to view the desired Point Status table.

4. On

the

Point

Status

table

press

NEXT

or

PREVIOUS until desired point is displayed on the screen.

For Discrete Points — Press

START

or

STOP ,

YES or NO , ON or OFF , etc. to select the desired

state.

For

Analog

Points

Press

INCREASE

or

DECREASE to select the desired value.

5. Press ENTER to register new value.

OVERRIDE OPERATIONS
NOTE: When overriding or changing metric values, it is nec-
essary to hold the softkey down for a few seconds in order
to see a value change, especially on kilopascal values.

To Remove an Override
1. On

the

Point

Status

table

press

NEXT

or

PREVIOUS to highlight the desired point.

2. Press SELECT to access the highlighted point.

3. Press RELEASE to remove the override and return the

point to the PIC’s automatic control.

Override Indication — An override value is indicated by
‘‘SUPVSR,’’ ‘‘SERVC,’’ or ‘‘BEST’’ flashing next to the point
value on the Status table.

TO VIEW OR CHANGE TIME SCHEDULE OPERATION
(Fig. 14)

1. On the Menu screen, press SCHEDULE .

2. Press NEXT or PREVIOUS to highlight one of the

following schedules.

OCCPC01S — LOCAL Time Schedule
OCCPC02S — ICE BUILD Time Schedule
OCCPC03-99S — CCN Time Schedule (Actual

number is defined in CONFIG table.)

3. Press SELECT to access and view the time schedule.

4. Press NEXT or PREVIOUS to highlight the de-

sired period or override that you wish to change.

5. Press SELECT to access the highlighted period or

override.

Fig. 14 — Example of Time Schedule

Operation Screen

18