Table 3 — Protective Safety Limits and Control Settings

MONITORED PARAMETER

LIMIT

APPLICABLE COMMENTS

TEMPERATURE SENSORS
OUT OF RANGE

–40 to 245 F (–40 to 118.3 C)

Must be outside range for 2 seconds

PRESSURE TRANSDUCERS
OUT OF RANGE

0.08 to 0.98 Voltage Ratio

Must be outside range for 2 seconds.
Ratio = Input Voltage ÷ Voltage Reference

COMPRESSOR DISCHARGE
TEMPERATURE

Ͼ

220 F (104.4 C)

Preset, alert setting configurable

BEARING TEMPERATURE

Ͼ

220 F (104.4 C)

Preset, alert setting configurable

EVAPORATOR REFRIGERANT
TEMPERATURE
(Temp converted from Pressure
Reading)

Ͻ

33 F (for water chilling) (0.6° C)

Preset, configure chilled medium for water
(Service1 table)

Ͻ

Brine Refrigerant Trippoint (set point adjustable

from 0 to 40 F [–18 to 4 C] for brine chilling)

Configure chilled medium for brine (Service1
table). Adjust brine refrigerant trippoint for
proper cutout

TRANSDUCER VOLTAGE

Ͻ

4.5 vdc

Ͼ

5.5 vdc

Preset (Read voltage at terminals 34 and 35
on PSIO module)

CONDENSER PRESSURE — SWITCH

Ͼ

218 ± 7 psig (1503 ± 48 kPa),

reset at 120 ± 10 (827 ± 69 kPa)

Preset

— CONTROL

215 psig (1482 kPa)

Preset

COMPRESSOR OIL PRESSURE — SWITCH

Cutout

Ͻ

11 psid (76 kPad) ± 1.5 psid (10.3 kPad)

Cut-in

Ͼ

16.5 psid (114 kPad) ± 4 psid (27.5 kPad)

Preset, no calibration needed

— CONTROL

Cutout

Ͻ

15 psid (103 kPad)

Alert

Ͻ

18 psid (124 kPad)

Preset

LINE VOLTAGE — HIGH

Ͼ

110% for one minute

Preset, based on transformed line voltage to
24 vac rated-input to the Starter Management
Module. Also monitored at PSIO power input.

— LOW

Ͻ

90% for one minute or

р

85% for 3 seconds

— SINGLE-CYCLE

Ͻ

50% for one cycle

COMPRESSOR MOTOR LOAD
(% Compressor Amps)

Ͼ

110% for 30 seconds

Preset

Ͻ

10% with compressor running

Preset

Ͼ

10% with compressor off

Preset

STARTER ACCELERATION TIME
(Determined by inrush current
going below 100% compressor
motor load)

Ͼ

45 seconds

For chillers with reduced voltage mechanical
and solid-state starters

Ͼ

10 seconds

For chillers with full voltage starters
(Configured on Service1 table)

STARTER TRANSITION

Ͼ

75 seconds

Reduced voltage starters only

CONDENSER FREEZE
PROTECTION

Energizes condenser pump relay if condenser refrigerant tem-
perature or condenser entering water temperature is below the
configured condenser freeze point temperature. Deenergizes
when the temperature is 5 F (3 C) above condenser freeze point
temperature.

CONDENSER FREEZE POINT configured in
Service01 table with a default setting of
34 F (1 C).

IMPELLER CLEARANCE

Displacement switch open

Thrust movement excessive

MOTOR LEAK DETECTOR (TEWAC
MOTORS ONLY)

Water from motor cooling is leaking

Water sensors are installed only on open-drive
motors that use water cooling. (Totally enclosed,
water-to-air cooled [TEWAC] motors)

GEAR OIL TEMPERATURE
— CONTROL

Cut-Out > 150 F (66 C)
Alert > 130-145 (54 - 63 C)

Preset
Adjustable

GEAR OIL PRESSURE
—CONTROL

Cut-out < 12 psi (83 kPa)
Alert < 15-20 psi (103 - 139 kPa)

Preset
Adjustable

FLOW SWITCHES (Field Supplied)

Operate water pumps with chiller off. Manually reduce water flow and observe
switch for proper cutout. Safety shutdown occurs when cutout time exceeds
3 seconds.

CUT-OFF
SETTING
ADJUSTMENT
SCREW

Carrier Part No. HK06ZC001

NOTE: Dimensions in parentheses are in
millimeters.

Carrier Part No. HK06ZC033