Table 2 — LID Display Data (cont)
EXAMPLE 6 — CONFIGURATION (CONFIG) DISPLAY SCREEN
To access this display from the LID default screen:
1. Press
MENU
.
2. Press SERVICE .
3. Scroll down to highlight EQUIPMENT CONFIGURATION.
4. Press SELECT .
5. Scroll down to highlight CONFIG.
6. Press SELECT .
DESCRIPTION
CONFIGURABLE RANGE
UNITS
REFERENCE POINT NAME
DEFAULT VALUE
RESET TYPE 1
Degrees Reset at 20 mA
–30-30 (–17-17)
DEG F (DEG C)
deg
20ma
10
⌬
(6
⌬
)
RESET TYPE 2
Remote Temp (No Reset)
–40-245 (–40-118)
DEG F (DEG C)
res
rt1
85 (29)
Remote Temp (Full Reset)
–40-245 (–40-118)
DEG F (DEG C)
res
rt2
65 (18)
Degrees Reset
–30-30 (–17-17)
DEG F (DEG C)
res
rt
10
⌬
(6
⌬
)
RESET TYPE 3
CHW Delta T (No Reset)
0-15 (0-8)
DEG F (DEG C)
restd
1
10
⌬
(6
⌬
)
CHW Delta T (Full Reset)
0-15 (0-8)
DEG F (DEG C)
restd
2
0
⌬
(0
⌬
)
Degrees Reset
–30-30 (–17-17)
DEG F (DEG C)
deg
chw
5
⌬
(3
⌬
)
Select/Enable Reset Type
0-3
res
sel
0
ECW CONTROL OPTION
DISABLE/ENABLE
ecw
opt
DISABLE
Demand Limit At 20 mA
40-100
%
dem
20ma
40
20 mA Demand Limit Option
DISABLE/ENABLE
dem
sel
DISABLE
Auto Restart Option
DISABLE/ENABLE
astart
DISABLE
Remote Contacts Option
DISABLE/ENABLE
r
contact
DISABLE
Temp Pulldown Deg/Min
2-10
tmp
ramp
3
Load Pulldown %/Min
5-20
kw
ramp
10
Select Ramp Type:
0/1
ramp
opt
1
Temp = 0, Load = 1
Loadshed Group Number
0-99
ldsgrp
0
Loadshed Demand Delta
0-60
%
ldsdelta
20
Maximum Loadshed Time
0-120
MIN
maxldstm
60
CCN Occupancy Config:
Schedule Number
3-99
occpcxxe
3
Broadcast Option
DISABLE/ENABLE
occbrcst
DISABLE
ICE BUILD Option
DISABLE/ENABLE
ibopt
DISABLE
ICE BUILD TERMINATION
0 =Temp, 1 =Contacts, 2 =Both
0-2
ibterm
0
ICE BUILD Recycle Option
DISABLE/ENABLE
ibrecyc
DISABLE
NOTE:
⌬
= delta degrees.
26