4 installing the 2h22-08r, 1 tabletop and shelf installations, Installing the 2h22-08r -3 3.4.1 – Cabletron Systems 2208 User Manual

Page 29: Tabletop and shelf installations -3, Section 3.4

background image

Installing the 2H22-08R

2H22-08R SmartSwitch 2208 User’s Guide

Page 3-3

3.4

INSTALLING THE 2H22-08R

The 2H22-08R may be installed on a tabletop, shelf, or in a 19-inch rack.

Section 3.4.1

provides the rules and instructions for a tabletop and shelf

installations, and

Section 3.4.2

provides the rules and instructions for a

rackmount installation.

3.4.1

Tabletop and Shelf Installations

Tabletop and shelf installations must be within reach of the network
cabling and meet the requirements listed below:

Locate the 2H22-08R within seven feet of an appropriately grounded
power source and an unrestricted surface area as shown in

Figure 3-1

that meets the power supply requirements listed in

Appendix A

.

In a shelf installation, the shelf must support 13.6 kg (30 lb) of static
weight for each 2H22-08R.

Maintain a temperature of between 5°C (41°F) and 40°C (104°F) at
the installation site with fluctuations of less than 10°C (18°F) per hour.

Figure 3-1

Tabletop or Shelf Installation

!

CAUTION

To ensure proper ventilation and prevent overheating, leave a
minimum clearance space of 5.1 cm (2.0 in) at the left, right,
and rear of the 2H22-08R.

2251-06

A = 15 cm (6 in)
B = 45 cm (22.5 in)
C = 53 cm (21 in)

C

B

A

D

D = 213 cm (7 ft)

7

8

1X

5X

6X

4X

3X

2X

2

1

6

5

4

3

PWR

CPU

COM

RESET

2H22-08R