Updating Firmware Images and Monitoring the PDU Power Status

Viewing or Changing the PMC Configuration Information

The PMC configuration information is stored in the PDU PMC board’s

internal EEPROM. The PMC configuration file is a text (TXT) file. You must

use TFTP server to retrieve the configuration data and then use Notepad or a

text editor to view or change the configuration data.
For example, a configuration data should have the following information:

Configuring the SNMP Traps

1 Import the PDU PMC configuration data.
2 Use a Notepad or text editor to edit the configuration data.
3 Enter an IP address in the appropriate Trap Destination field.
4 Set the SNMP read community string in SNMP RD COMMUNITY STR.

By default, the SNMP read community string is public.

5 Set the SMP read-write community string in SNMP RW COMMUNITY

STR. By default, the SNMP read-write community string is private.

6 Save the file.
7 Use the TFTP server software to upload the configuration file.

CONNECT.TYPE=STATIC/DHCP
IP=192.168.0.120
NETMASK=255.255.255.0
GATEWAY=192.168.0.1
TRAP.DESTINATION1=0.0.0.0
TRAP.DESTINATION2=0.0.0.0
TRAP.DESTINATION3=0.0.0.0
TRAP.DESTINATION4=0.0.0.0
TRAP.DESTINATION5=0.0.0.0
SNMP.RD.COMMUNITY.STR=public
SNMP.RW.COMMUNITY.STR=private
MANAGE.ACSOCKET.A.DEFAULT.POWER=ON/OFF
MANAGE.ACSOCKET.B.DEFAULT.POWER=ON/OFF
MANAGE.ACSOCKET.C.DEFAULT.POWER=ON/OFF
MANAGE.PDU.DEFAULT.POWER=ON/OFF
MANAGE.PSU.CONFIGURATION=5+1