4.2 Mandatory Mounting, Cooling, and Airflow Provisions
ClearCube Technology, Inc.
35
4.2.2.1 Desktop Mounting
When placing a zero client on top of a desk or other flat, unenclosed surface, ensure that:
The open vent faces up (as described in the following section)
There is at least 4 inches of space around edges of the zero client.
There is open space above the zero client.
You do not stack any objects on top of the zero client, including any paper or USB
peripherals (such as hard drives).
Ambient temperature never exceeds 35° C, including in enclosed environments that can
elevate temperatures, such as under a desk, on a shelf, or inside a drawer.
Zero client vents are flat—not standing vertically—as shown in the following figure.
The zero client is not in any enclosed areas, such as:
A desk drawer
A cable tray in a desk
Adjacent walls and furniture, such as file drawers, desk supports, and chairs, do not block or
enclose any sides of the zero client.
Figure 16. Adjacent wall restricting airflow around zero client
Ensure that a device mounted
under a desk is not adjacent to a
wall. This configuration prevents
proper air flow and cooling.
Overhead View of Desk with Zero
Client Mounted Adjacent to Wall