Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual
Page 88
![background image](/manuals/581626/88/background.png)
8-8
DeviceNet Adapter for use with DPI AC Drives
6
EEPROM
Sum Flt
The EEPROM in the adapter is corrupt.
7
Online @
125 kbps
The adapter and DPI product are communicating at
125 kbps.
8
Online @
500 kbps
The adapter and DPI product are communicating at
500 kbps.
9
Bad Host Flt
The adapter was connected to an incompatible
product.
10
Dup. Port Flt
Another peripheral with the same port number is
already in use.
11
Type 0 Login
The adapter has logged in for type 0 control.
12
Type 0 Time
Flt
The adapter has not received a type 0 status
message within the specified time.
13
DL Login
The adapter has logged into a Datalink.
14
DL Reject Flt
The host rejected an attempt to log in to a Datalink
because the Datalink is not supported or is used by
another peripheral.
15
DL Time Flt
The adapter has not received a Datalink message
within the specified time.
16
Control
Disabled
The adapter has sent a “Soft Control Disable”
command to the DPI product.
17
Control
Enabled
The adapter has sent a “Soft Control Enable”
command to the DPI product.
18
PCCC IO Time
Flt
The adapter has not received a PCCC control
message within the specified time-out interval.
19
Normal
Startup
The adapter successfully started up.
20
Message
Timeout
A client-server message sent by the peripheral was
not completed.
21
DPI Fault Msg The DPI Host has faulted.
22
DN Poll
Timeout
A polled I/O connection has timed out.
23
DN I/O Too
Long
Reconfigure the I/O length in the scanner.
24
Bad I/O
Fragment
A DeviceNet I/O fragment was received out of
sequence. Possible line noise problem.
Table 8.5 – Event Codes and Descriptions (Continued)
Code
Event Description