E-6

DeviceNet Adapter for use with DPI AC Drives

E.2 M-S Output Parameter Configurations

M-S Output (26) has five configurable bits as shown in figure E.2.

When you enable Cmd/Ref or Datalink in the adapter, you must set
the corresponding bit in M-S Output (26) if you want the output data
to be sent to the scanner or master device.

Tables E.3 and E.4 list possible configurations for M-S Output (26)
and the possible data size allocation associated with each value
depending on the method of data transfer.

Figure E.2 – Bits and Corresponding I/O

Table E.3 – Host Products using 16-bit Reference/Feedback and

Datalinks

M-S

Input

M-S

Output

Allocation (Number of Bytes)

Data Size sent from the Adapter to the

Controller

Poll
Only

COS
Only

Cyclic
Only

Poll &
COS

Poll &
Cyclic

xxxxx

00000

0

NA

NA

NA

NA

xxxxx

00010

4

NA

NA

NA

NA

xxxxx

00100

4

NA

NA

NA

NA

xxxxx

00110

8

NA

NA

NA

NA

xxxxx

01000

4

NA

NA

NA

NA

xxxxx

01010

8

NA

NA

NA

NA

xxxxx

01100

8

NA

NA

NA

NA

xxxxx

11100

12

NA

NA

NA

NA

xxxxx

10000

4

NA

NA

NA

NA

xxxxx

10010

8

NA

NA

NA

NA

xxxxx

10100

8

NA

NA

NA

NA

xxxxx

10110

12

NA

NA

NA

NA

xxxxx

11000

8

NA

NA

NA

NA

xxxxx

11010

12

NA

NA

NA

NA

xxxxx

11100

12

NA

NA

NA

NA

xxx0, 0000

Datalink D

Datalink C

Datalink B

Datalink A

Cmd/Ref

0 = Peer or other output
1 = Master-Slave output