Using Explicit Messaging

7-13

Ladder Logic Program

Important: To originate a scanner transaction, use a copy operation

to M0:[slot number]:224. Then, use a copy operation to
read M1:1.224 for the result. If more than one message
is enabled, use the TXID to determine which message
you are reading.

Figure 7.9 – Sample SLC Ladder Logic Program

0000

B3:0

0

COP

#N20:10

#M0:1:224

32

U

B3 :0

0

Initiate
Explicit
Message

0001

I:1.0

15

1747-SDN

Explicit
Message
Response
Available

COP

Copy File
Source

#M1:1:224

Dest

#N20:50

Length

32

Explicit
Message
Response

EQU

Equal
Source A

N20:10

257 <

Source B

N20:50

257 <

MVM

Mask Move
Source

N20:0

4<

Mask

00FFh

255 <

Dest

M0:1.224

?<

Explicit
Message

0002

END

Initiate
Explicit
Message

Explicit
Message

Copy File
Source
Dest
Length

When B3:0/0 is set to true, this rung will
copy the 32 words of Explicit Message from
the buffer at N20:10 to M0-File Explicit
Message buffer. The scanner will send the
message out over DeviceNet.

When I:1.0/15 is set to true and the Explicit
Message Response has been received in the
M1-File, this rung performs the following:
- Copies the response message into N10:50.
- Copies a command of four (4) into the

M1-File.The four (4) commands the 1747-SDN
scanner to discard the response data so that the
buffer can be used for the next message
response.