beautypg.com

Rockwell Automation RECOMM-DNET DeviceNet Adapter for use with DPI AC Drives User Manual

Page 38

background image

4-14

DeviceNet Adapter for use with DPI AC Drives

Step 7. Set Peer Inp Timeout (36) to the maximum amount of time

the adapter will wait for a message before timing out. See
figure 4.21.

Important: This value must be greater than the product of Peer Out

Time (42) multiplied by Peer Out Skip (43) in the
adapter from which you are receiving I/O.

Step 8. Peer Flt Action (34) specifies the action that the adapter

will take if it times out. See figure 4.22. For details, refer to
section 4.9.

Figure 4.20 – Peer Reference Adjust Screen on an LCD OIM

Figure 4.21 – Minimum Peer Receiving Time Screen on an LCD OIM

!

ATTENTION: Peer Flt Action (34) lets you determine
the action of the adapter and connected drive if
communications are disrupted. By default, this
parameter faults the drive. You can set this
parameter so that the drive continues to run.
Precautions should be taken to ensure that the
setting of this parameter does not create a hazard
of injury or equipment damage. Failure to observe
these precautions could result in bodily injury or
damage to equipment.

Port 5 Device

RECOMM-DNET

Parameter #: 33

Peer Ref Adjust

0.00

%

0.00 <> 199.99

Default = 0.00%

Port 5 Device

RECOMM-DNET

Parameter #: 36

Min Peer Rx Time

1

0.00

Secs.

0.01 <> 180.00

Default = 10.00 Secs