Read controller tags – Rockwell Automation 1768-EWEB EtherNet/IP Web Server Module User Manual User Manual
Page 94
![background image](/manuals/581540/94/background.png)
Publication ENET-UM527E-EN-P - October 2006
94 Create Custom Web Pages
Read Controller Tags
There are two ASP functions you can use to read controller tags:
Function:
ReadLogixTag(path, tagname, tagtype)
The
ReadLogixTag
function connects to a controller at a specified
path
, retrieves the value of a tag with a name
tagname
and of
tagtype
.
Parameters:
Example:
For example, retrieve a DINT tag named ’my_dint_tag’ from a
controller in slot 3 of the local chassis:
"my_dint_tag" value:
<% ReadLogixTag("1,3", "my_dint_tag", "DINT"); %>
Function:
ReadLogixTagUnconnected(path, tagname, tagtype)
The
ReadLogixTagUnconnected
function performs the same task as
ReadLogixTag
function and uses the same parameters. This function,
however, retrieves the tag value through unconnected messaging,
rather than connected messaging.
If You Want
Use This ASP Function
See Page
Connected messaging
ReadLogixTag
Unconnected messaging
ReadLogixTagUnconnected
Parameter
Description
path
The path is a CIP path, with no spaces, and segments separated by commas. For example:
tagname
The tagname identifies a controller-scoped tag.
tagtype
The tagtype must be an atomic type (BOOL, SINT, INT, DINT, REAL) or string. Use standard
dot notation to specify a member of an array or a user-defined structure (for example,
’timer1.ACC’ for the accumulator of a timer tag named ’timer1’).
Path Example
Description
1,3
1 = backplane
3 = slot 3