Chapter 4, Use data views to access controller data, About this chapter – Rockwell Automation 1768-EWEB EtherNet/IP Web Server Module User Manual User Manual
Page 55: Data views overview, About this chapter data views overview, Chapter
55
Publication ENET-UM527E-EN-P - October 2006
Chapter
4
Use Data Views to Access Controller Data
About This Chapter
The module provides access to controller data for monitoring and
data modification of controller tags.
This chapter shows you how to set up data views of controller tags.
For data views, the module must be in the same chassis as the
controller.
Data Views Overview
Data views give you the ability to read from and write to RSLogix
controller tags from a browser interface or an external application.
The module provides web pages that let you configure a set of tags (a
data view) that can be read or written.
A data view consists of an XML file with data tag information The XML
file is in a readable ASCII format. It contains the tag name, data type,
path, display formatting, and privilege access level. Each tag value is
exposed as a separate element and an error attribute is optional.
Topic
Page
Monitor Data Views and Tag Data
Use an External Application to Access Data Views
Example: Data View XML with Tag Values