74 DeviceNet Information
Transition to Program Mode
Parameter values can only be downloaded to an XM module while the module
is in Program mode. Any attempt to download a parameter value while the
module is in Run mode will result in a Device State Conflict error.
To transition an XM module from Run mode to Program mode on a
DeviceNet network, set the Device Mode parameter to "Program mode" and
click Apply. Note that you cannot change any other parameter until you have
downloaded the Program mode parameter.
Refer to your DeviceNet documentation for specific instructions on editing
EDS device parameters.
Transition to Run Mode
In order to collect data and monitor measurement devices, XM modules must
be in Run mode. To transition an XM module from Program mode to Run
mode on a DeviceNet network, set the Device Mode parameter to "Run
mode" and click Apply.
Refer to your DeviceNet documentation for specific instructions on editing
EDS device parameters.
TIP
The Module Status indicator flashes green when the
module is in Program mode.
TIP
You can also use the Stop service described on page 75 to
transition XM modules to Program mode.
TIP
The Module Status indicator is solid green when the
module is in Run mode.
TIP
You can also use the Start service described on page 75 to
transition XM modules to Run mode.