Module indicators, Module status (ms) indicator – Rockwell Automation 1440-TPS02-01RB XM-320 Position Module User Manual
Page 49
Publication GMSI10-UM005C-EN-P - May 2010
Installing the XM-320 Position Module 41
Module Indicators
The XM-320 has six LED indicators, which include a module status (MS)
indicator, a network status (NS) indicator, a status indicator for each channel
(CH1 and CH2), an activation indicator for the Setpoint Multiplier, and a
status indicator for the Relay. The LED indicators are located on top of the
module.
Figure 2.26 LED Indicators
The following tables describe the states of the LED status indicators.
Module Status (MS) Indicator
1
Program Mode - Typically this occurs when the module configuration settings are being updated with the XM
Serial Configuration Utility. In Program Mode, the module does not perform its usual functions. The signal
processing/measurement process is stopped, and the status of the alarms is set to the disarm state to prevent
a false alert or danger status.
2
Run Mode - In Run Mode, the module collects measurement data and monitors each measurement device.
POSITION
1440-TPS02-01RB
Module Indicators
Color
State
Description
No color
Off
No power applied to the module.
Green
Flashing Red
Module performing power-up self test.
Flashing
Module operating in Program Mode
1
.
Solid
Module operating in Run Mode
2
.
Red
Flashing
•
Application firmware is invalid or not loaded.
Download firmware to the module.
•
Firmware download is currently in progress.
•
The module power voltage is incorrect.
Solid
An unrecoverable fault has occurred. The module may
need to be repaired or replaced.