56 Configuration Parameters
Condition
Controls when the alarm should trigger.
•
Greater than - Triggers the alarm when the
measurement value is greater than or equal to the
Alert and Danger Threshold values.
The Danger Threshold value must be greater than
or equal to the Alert Threshold value for the trigger
to occur.
•
Less than - Triggers the alarm when the
measurement value is less than or equal to the
Alert and Danger Threshold values.
The Danger Threshold value must be less than or
equal to the Alert Threshold value for the trigger to
occur.
•
Inside range - Triggers the alarm when the
measurement value is equal to or inside the range
of the Alert and Danger Threshold values.
The Danger Threshold (High) value must be less
than or equal to the Alert Threshold (High) value
AND the Danger Threshold (Low) value must be
greater than or equal to the Alert Threshold (Low)
value for the trigger to occur.
•
Outside range - Triggers the alarm when the
measurement value is equal to or outside the
range of the Alert and Danger Threshold values.
The Danger Threshold (High) value must be greater
than or equal to the Alert Threshold (High) value,
AND the Danger Threshold (Low) value must be
less than or equal to the Alert Threshold (Low)
value for the trigger to occur.
Options: Greater Than
Less Than
Inside Range
Outside Range
Alert Threshold (High)
The threshold value for the alert (alarm) condition.
Note: This parameter is the greater (High) threshold
value when Condition is set to "Inside Range" or
"Outside range."
Same measurement unit as Output
Data Unit selection for specified
channel.
Danger Threshold (High)
The threshold value for the danger (shutdown)
condition.
Note: This parameter is the greater (High) threshold
value when Condition is set to "Inside Range" or
"Outside Range."
Same measurement unit as Output
Data Unit selection for specified
channel.
Alert Threshold (Low)
The lesser threshold value for the alert (alarm)
condition.
Note: This value is not used when Condition is set
to "Greater Than" or "Less Than."
Same measurement unit as Output
Data Unit selection for the specified
channel.
Danger Threshold (Low)
The lesser threshold value for the danger (shutdown)
condition.
Note: This value is not used when Condition is set
to "Greater Than" or "Less Than."
Same measurement unit as Output
Data Unit selection for the specified
channel.
Alarm Parameters
Parameter Name
Description
Values/Comments