Rockwell Automation 1440-TPS02-01RB XM-320 Position Module User Manual
Page 108

Publication GMSI10-UM005C-EN-P - May 2010
100 DeviceNet Objects
6
Get
Threshold Units
USINT
Indicates whether the
threshold and hysteresis
value are specified in
units of measure.
Set to 1
1 = Measurement units
7
Get/Set
Condition
USINT
Indicates on which side of
the threshold values the
alarm and danger
conditions exist.
0 = Greater than
1 = Less than
2 = Inside range
3 = Outside range
8
Get/Set
Alert Threshold
(High)
REAL
The threshold value for
the alert (alarm) condition
(greater threshold for
range types).
9
Get/Set
Danger Threshold
(High)
REAL
The threshold value for
the danger (shutdown)
condition (greater
threshold for range types).
10
Get/Set
Alert Threshold
Low
REAL
The lesser threshold value
for the alert (alarm)
condition for the range
condition types.
11
Get/Set
Danger Threshold
Low
REAL
The lesser threshold value
for the danger (shutdown)
condition for the range
condition types.
12
Get/Set
Hysteresis
REAL
The amount on the safe
side of a threshold by
which the value must
recover to clear the alarm.
13
Get/Set
Threshold (Setpoint
Multiplier)
REAL
Indicates how the
thresholds should be
adjusted when the
setpoint multiplication
function is invoked.
0 = Disable alarm
> 0 = Multiply the thresholds by
the value
14
Get/Set
Startup Period
UINT
The amount of time that
the Threshold (Setpoint)
Multiplier is applied after
the startup signal is
received.
Seconds
18
Get/Set
Name
STRING2
A name to help identify
this alarm.
Table C.31 Alarm Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics